EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1 – 2019.12
Setup
A Main leaving water temperature zone
B One single room
a Remote controller of the heat pump convectors
The heat pump convectors are directly connected to the indoor unit.
The desired room temperature is set via the remote controller of the heat pump
convectors.
The space heating/cooling demand signal is sent to one digital input on the
indoor unit (X2M/35 and X2M/30).
The space operation mode is sent to the heat  pump convectors by one digital
output on the indoor unit (X2M/4 and X2M/3).
INFORMATION
When using multiple heat  pump convectors, make sure each one receives the
infrared signal from the remote controller of the heat pump convectors.
Configuration
Setting
Unit temperature control:
#: [2.9]
Code: [C-07]
Number of water temperature zones:
#: [4.4]
Code: [7-02]
External room thermostat for the main
zone:
#: [2.A]
Code: [C-05]
Benefits
Cooling. The heat pump convector offers, besides heating capacity, also excellent
cooling capacity.
Efficiency. Optimal energy efficiency because of the interlink function.
Stylish.
5
Application guidelines
|
B
A
a
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
0 (Single zone): Main
1 (1 contact): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
Value
Installer reference guide
29