11.6 To inspect the inside of the domestic hot water tank

EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1 – 2019.12
1
7 Tightening torques for installation:
Tube connection
Temperature and pressure relief valve
DANGER: RISK OF BURNING
The water in the tank can be very hot.
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Close the cold water supply.
Prerequisite: Open all the hot water tapping points to allow air to enter the
system.
Prerequisite: Remove the top panel. See
1 Remove the clip that fixes the domestic hot water OUT pipe.
2 Disconnect the pipe such that the tank is accessible for visual inspection (e.g.
with an endoscope).
11
2
Item
"7.2.3 To open the indoor
Maintenance and service
|
Tightening torque
30 N•m
40 N•m
unit" [
Installer reference guide
4
 67].