EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1 – 2019.12
Formula
COP = (Electricity price / gas price)
boiler efficiency
(a)
Make sure to use the same units of measurement for the electricity price and gas
price (example: both c€/kWh).
2 Determine the value of [C‑03] using the graph. For an example, see the table
legend.
COP
6
5
4
3
2
1
0
-14
-12
-10
-8
-6
a
[C‑03]=2.5 in case of COP=3 and LWT=35°C
b
[C‑03]=10.5 in case of COP=3 and LWT=55°C
NOTICE
Make sure to set the value of [5‑01] at least 1°C higher than the value of [C‑03].
Electricity and gas prices
INFORMATION
To set electricity and gas price values, do NOT use overview settings. Set them in the
menu structure instead ([7.5.1], [7.5.2], [7.5.3], and [7.6]). For more information on
how to set the energy prices, see the operation manual and the user reference
guide.
INFORMATION
Solar panels. If solar panels are used, set the electricity price value very low to
promote the use of the heat pump.
#
Code
[7.5.1]
N/A
[7.5.2]
N/A
[7.5.3]
N/A
[7.6]
N/A
(a)
×
If:
Electricity price: 20 c€/kWh
Gas price: 6 c€/kWh
Boiler efficiency: 0.9
Then: COP = (20/6)×0.9 = 3
-4
-2
0
2
4
6
8
10
2.5 (a)
10.5 (b)
User settings > Electricity price >
High
User settings > Electricity price >
Medium
User settings > Electricity price >
Low
User settings > Gas price
8
Configuration
|
Example
12
14
Description
Installer reference guide
163