Daikin Altherma 3 H F Installer's Reference Manual page 123

Hide thumbs Also See for Altherma 3 H F:
Table of Contents

Advertisement

EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1 – 2019.12
#
Code
[2.8.1]
[9-01]
[2.8.2]
[9-00]
[2.8.3]
[9-02]
[2.8.4]
[9-03]
Control
Define how the operation of the unit is controlled.
Control
Leaving water
External room
thermostat
Room thermostat
#
Code
[2.9]
[C‑07]
Thermostat type
Only applicable in external room thermostat control.
NOTICE
If an external room thermostat is used, the external room thermostat will control the
room frost protection. However, the room frost protection is only possible if [C.2]
Space heating/cooling=On.
Heating minimum:
15°C~37°C
Heating maximum:
[2‑0C]=2 (emitter type main zone = radiator)
37°C~70°C
Otherwise: 37°C~55°C
Cooling minimum:
5°C~18°C
Cooling maximum:
18°C~22°C
In this control...
Unit operation is decided based on the leaving water
temperature regardless the actual room temperature
and/or heating or cooling demand of the room.
Unit operation is decided by the external thermostat or
equivalent (e.g. heat pump convector).
Unit operation is decided based on the ambient
temperature of the user interface used as a room
thermostat.
0: Leaving water
1: External room thermostat
2: Room thermostat
8
Configuration
|
Description
Description
Installer reference guide
123