Summary of Contents for Daikin Altherma 3 H F
Page 1
Installation manual Daikin Altherma 3 H F EAVZ16S18DA6V(7) EAVZ16S23DA6V(7) Installation manual EAVZ16S18DA9W English Daikin Altherma 3 H F EAVZ16S23DA9W...
7.3.1 What is a weather-dependent curve? ......20 Latest revisions of the supplied documentation may be available on 7.3.2 2-points curve ............. 21 the regional Daikin website or via your dealer. 7.3.3 Slope-offset curve ............21 EAVZ16S18+23DA6V(7)+9W Installation manual Daikin Altherma 3 H F...
Due to the presence of glycol, corrosion of the system is Daikin website (publicly accessible). possible. Uninhibited glycol will turn acidic under the ▪ The full set of latest technical data is available on the Daikin influence of oxygen. This process is accelerated by the Business Portal (authentication required).
Front panel continuously operating ignition sources (example: open High voltage switch box cover flames, an operating gas appliance or an operating electric Open heater). 1 Remove the top panel. EAVZ16S18+23DA6V(7)+9W Installation manual Daikin Altherma 3 H F 4P556073-1A – 2021.09...
"4.2.2 To lower the switch box on the indoor drain" [ 4 7] ▪ "4.3.2 To connect the drain hose to the ▪ When you need access to the high voltage switch box Installation manual EAVZ16S18+23DA6V(7)+9W Daikin Altherma 3 H F 4P556073-1A – 2021.09...
3× 3 Slide the indoor unit into position. 4 Adjust the height of the leveling feet to compensate for floor irregularities. The maximum allowed deviation is 1°. ≤1° EAVZ16S18+23DA6V(7)+9W Installation manual Daikin Altherma 3 H F 4P556073-1A – 2021.09...
Water OUT to outdoor unit (screw connection, 1") 7H). NOTICE It is recommended to install shut-off valves to domestic cold water in and domestic hot water out connections. These shut-off valves are field supplied. Installation manual EAVZ16S18+23DA6V(7)+9W Daikin Altherma 3 H F 4P556073-1A – 2021.09...
▪ galvanized pipes are NOT used in glycol systems since 4 Reattach the top panel. the presence may lead to the precipitation of certain components in the glycol's corrosion inhibitor. EAVZ16S18+23DA6V(7)+9W Installation manual Daikin Altherma 3 H F 4P556073-1A – 2021.09...
Adding glycol to the water circuit reduces the maximum allowed Electrical installation water volume of the system. For more information, see the installer reference guide (topic "To check the water volume and flow rate"). DANGER: RISK OF ELECTROCUTION Installation manual EAVZ16S18+23DA6V(7)+9W Daikin Altherma 3 H F 4P556073-1A – 2021.09...
Heat pump convector 100 mA Field supplied components Shut-off valve 100 mA Electricity meter 2 (per meter) Domestic hot water pump Alarm output Changeover to external heat source control EAVZ16S18+23DA6V(7)+9W Installation manual Daikin Altherma 3 H F 4P556073-1A – 2021.09...
(X5M/9+10) as the safety thermostat for the additional zone. It is only possible for the system to have EITHER preferential kWh rate power supply OR a safety thermostat for the additional zone. Installation manual EAVZ16S18+23DA6V(7)+9W Daikin Altherma 3 H F 4P556073-1A – 2021.09...
2 Fix the cable with cable ties to the cable tie mountings. 6.3.8 To connect the alarm output 1 Connect the alarm output cable to the appropriate terminals as shown in the illustration below. Installation manual EAVZ16S18+23DA6V(7)+9W Daikin Altherma 3 H F 4P556073-1A – 2021.09...
(delivered as accessory). Without low voltage cables With low voltage cables 2 Fix the cable with cable ties to the cable tie mountings. EAVZ16S18+23DA6V(7)+9W Installation manual Daikin Altherma 3 H F 4P556073-1A – 2021.09...
▪ "7.5 Menu structure: Overview installer field settings. 7.1.1 To access the most used commands To change the user permission level You can change the user permission level as follows: Installation manual EAVZ16S18+23DA6V(7)+9W Daikin Altherma 3 H F 4P556073-1A – 2021.09...
(User settings > Time/date) once the unit is initialised. 7.2.3 Configuration wizard: System Indoor unit type The indoor unit type is displayed, but cannot be adjusted. EAVZ16S18+23DA6V(7)+9W Installation manual Daikin Altherma 3 H F 4P556073-1A – 2021.09...
2×[6‑03]+[6‑04]. An overpressure bypass valve can be integrated in the system. Keep in mind that this valve might not be shown on the illustrations. Installation manual EAVZ16S18+23DA6V(7)+9W Daikin Altherma 3 H F 4P556073-1A – 2021.09...
50°C, temperature – (Delta T)/2 Daikin recommends NOT to disable the backup heater This means that for a same leaving water temperature second step because it will have a big impact on the...
It therefore is connected to a temperature sensor on the North wall of the building. If the outdoor temperature drops or rises, the unit compensates instantly. Thus, the unit does not have to Installation manual EAVZ16S18+23DA6V(7)+9W Daikin Altherma 3 H F 4P556073-1A – 2021.09...
▪ Setpoint (X1, Y2) temperatures. ▪ Setpoint (X2, Y1) Examples Example Weather-dependent curve when slope is selected: Weather-dependent curve when offset is selected: EAVZ16S18+23DA6V(7)+9W Installation manual Daikin Altherma 3 H F 4P556073-1A – 2021.09...
To fine-tune the weather-dependent curve: 2-points curve [2.4] Main zone > Setpoint Weather dependent The following table describes how to fine-tune the weather- mode dependent curve of a zone or tank: Additional zone – Heating Installation manual EAVZ16S18+23DA6V(7)+9W Daikin Altherma 3 H F 4P556073-1A – 2021.09...
If an external room thermostat is used, the external room thermostat will control the room frost protection. However, the room frost protection is only possible if [C.2] Space heating/cooling=On. EAVZ16S18+23DA6V(7)+9W Installation manual Daikin Altherma 3 H F 4P556073-1A – 2021.09...
Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. Installation manual EAVZ16S18+23DA6V(7)+9W Daikin Altherma 3 H F 4P556073-1A – 2021.09...
6 Go to [8.4.A]: Information > Sensors > Flow There are NO damaged components or squeezed rate. pipes on the inside of the indoor and outdoor units. EAVZ16S18+23DA6V(7)+9W Installation manual Daikin Altherma 3 H F 4P556073-1A – 2021.09...
(domestic hot water mode). 1 Go to Stop UFH screed dryout. To monitor the temperatures: 2 Select OK to confirm. 1 In the menu, go to Sensors. 2 Select the temperature information. Installation manual EAVZ16S18+23DA6V(7)+9W Daikin Altherma 3 H F 4P556073-1A – 2021.09...
▪ Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. EAVZ16S18+23DA6V(7)+9W Installation manual Daikin Altherma 3 H F 4P556073-1A – 2021.09...
10 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). 10.1 Piping diagram: Indoor unit...
Normal kWh rate power supply Normal kWh rate power supply Main PCB Only for normal power supply Only for normal power supply * On/OFF thermostat (PC=power circuit) (standard) (standard) EAVZ16S18+23DA6V(7)+9W Installation manual Daikin Altherma 3 H F 4P556073-1A – 2021.09...
Page 30
Only for heat pump convector Normally open Normally open Only for wired On/OFF Only for wired On/OFF thermostat thermostat Safety thermostat Safety thermostat Only for wireless On/OFF Only for wireless On/OFF thermostat thermostat Installation manual EAVZ16S18+23DA6V(7)+9W Daikin Altherma 3 H F 4P556073-1A – 2021.09...
Page 31
A8P: X801M: 4-5 demand input 4 signal 2 core Only for BRC1HH* 2x0.75 X5M: 11-12 A14P: P1-P2 user interface communication 2 core 2x0.75 A13P: P1-P2 LAN adapter communication 4D120622A EAVZ16S18+23DA6V(7)+9W Installation manual Daikin Altherma 3 H F 4P556073-1A – 2021.09...
Page 32