Connecting The Chilled Water Inlet And Outlet Pipes; Connecting Seamless Steel Pipes - Huawei NetCol5000-C030H90D0 User Manual

In-row chilled water smart cooling product
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
Figure 3-32 Water inlet pipe (NetCol5000-C030/C032)
Step 3 Route the water inlet pipe from the inside to the outside through the water inlet
hole at the bottom of the smart cooling product.
Step 4 Clean the engineering pipes before connecting the water inlet pipe to the engineer
pipe to avoid impurities entering into the humidifier.
Step 5 Connect the water inlet pipe to the engineer pipe and wrap the pipe with thermal
insulation foam.
----End

3.8.3 Connecting the Chilled Water Inlet and Outlet Pipes

Context

3.8.3.1 Connecting Seamless Steel Pipes

Procedure
Step 1 Open the rear door and remove the air filter.
Issue 03 (2020-08-30)
NO TE
The other end is a reserved G 3/4 inch connector with inner screw threads. Connect the
other end to a rigid pipe based on site requirements.
A Y-shaped strainer has been installed on the chilled water inlet.
Connect the water inlet and outlet pipes from the inside to the outside and
from the bottom to the top.
Water inlet and outlet pipes are connected using thread connectors.
Chilled water inlet and outlet pipes can be connected in two ways. Select one
based on site requirements.
Copyright © Huawei Technologies Co., Ltd.
3 Installation
55