NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
5.
----End
Follow-up Procedure
After a USB flash drive has been inserted into the main control board USB port
and successfully identified, tap Export File under MIB File to export the MIB file
to the USB flash drive for the customer's use in accessing a third-party EMS.
Figure 4-16
Before using a USB flash drive, ensure that its data has been scanned by antivirus
software and is secure.
Figure 4-16 Exporting the MIB file successfully
4.4.5 Correlation Relationship of Parameters
When setting parameters, pay attention to the following relationships.
Alarm Parameters
●
●
Issue 03 (2020-08-30)
Figure 4-15 Setting SNMP trap parameters
Tap Submit under SNMP Trap.
shows successful file export.
NO TICE
Supply air high temperature alarm threshold + 5°C ≤ Return air high
temperature alarm threshold
Supply air high temperature alarm threshold + 5°C ≤ Hot aisle high
temperature alarm threshold
Copyright © Huawei Technologies Co., Ltd.
4 Commissioning
105