Figure 3-28 Securing the NetCol5000-C to the base
----End

3.8 Connecting Water Pipes

3.8.1 Connect Automatic Drainpipe

Context
● The external drainpipe must have a certain gradient (> 1:50), and no
accumulated water is allowed.
● The entire drainpipe should be closely wrapped with thermal insulation foam.
● The drainpipe can be secured along the door post using cable ties inside a
cabinet.
Procedure
Step 1 Remove the drainpipe plug.
Step 2 Install a pipe adapter and seal it with sealant.
Step 3 Connect the PPR water pipe using a heat gun and wrap the pipe with thermal
insulation foam.
Issue 03 (2020-08-30)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
3 Installation
52