NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)

2.4.3 Monitoring System

The monitoring system provides logic control, data collection, control demand
delivering, alarm reporting, data storage, user right management, and teamwork
control. You can connect the smart cooling product monitoring system to your
monitoring system over a northbound communications port to perform remote
management. The smart cooling product supports remote management ports and
provides RS485 ports and FE ports to support Modbus-RTU, Modbus-TCP and
SNMP for real-time data collection and alarm reporting.
Smart cooling products can be networked over the CAN bus to realize teamwork
control, energy conservation, and service life extension.

2.5 Typical Application Scenarios (NetCol5000-C065)

The NetCol5000-C provides a high-heat-flux cooling solution that applies to high-
density data centers or hot areas in common data centers. This section describes
the application scenario for the NetCol5000-C.
Figure 2-7 NetCol5000 in the contained cold aisle
(1) NetCol5000-C
Issue 03 (2020-08-30)
The controller intelligently identifies abnormal parameter settings (incorrect
commands) and rejects them automatically.
If the indoor temperature fluctuates beyond the normal range, an audible and
visible alarm signal is sent automatically.
Copyright © Huawei Technologies Co., Ltd.
2 Product Description
21