TABLE 11: Flare Nut Torque Recommendations
Outside
Diameter
Inches
mm
1/4"
6.35
3/8"
9.52
1/2"
12.70
5/8"
15.88
SECTION XIV: INDOOR UNIT
INSTALLATION
1. Shape the refrigerant line set so that it can be guided either out the
back of the indoor unit or through either side of the indoor unit
frame, then through the wall sleeve to the outside unit.
2. Pass the drain hose and refrigerant pipes through the wall hole then
set the indoor unit on the mounting bracket hooks by using the
markings at the top of the indoor unit as a guide.
A
MOUNTING PLATE
FIGURE 26: Indoor Unit Attachment to Mounting Bracket
3. Try moving the indoor unit to right and left to confirm that it is firmly
hooked on the installation plate.
4. While pressing the indoor unit onto the wall, hook it at the lower part
on the installation plate.
5. Carefully bend the bundle (line set, condensate line and cable) to
run along the outside wall toward the outdoor unit. Downward slope
of wall sleeve will ensure proper condensate drainage.
DO NOT RISE THE DRAIN HOSE
50 mm
OR MORE
DO NOT PUT THE
DRAIN HOSE END
INTO WATER
FIGURE 27: Proper and Improper Drain Hose Installation Application
Pull the indoor unit toward you to confirm that it is firmly hooked
on the mounting bracket.
For detaching the indoor unit from the installation plate, pull the indoor
unit toward you while pushing the bottom up at the specified places.
PUSH
FIGURE 28: Indoor Unit Removal
Johnson Controls Unitary Products
Recommended
Torque
English
Metric
(ft. - lb.)
(Newton Meter)
15 ft - lb.
20
26 ft - lb.
35
41 ft - lb.
55
48 ft - lb.
65
MARKING
DO NOT FORM THE DRAIN HOSE
INTO THE WAVED SHAPE
DO NOT PUT THE DRAIN
HOSE END IN THE
DRAINAGE CONTAINER
PUSH
6. Use the provided foam insulation to wrap the factory installed con-
densate line.
7. Connect indoor unit factory installed condensate line to field-pro-
vided condensate drain pipe.
8. Use tape approved for waterproofing line connections to secure the
field-provided pipe to the factory-installed condensate line.
9. Put water in the drain pan and make sure that the water is being
drained outside.
Install the drain pipe for proper drainage. Improper drainage can
result in water dripping inside the room.
SECTION XV: OUTDOOR UNIT
INSTALLATION
Refer to page 4 instructions when considering unit positioning and page
4 for condensate drainage requirements (heat pump).
SLAB OR ROOF MOUNTING
• Install the unit a minimum of 4 inches (102 mm) above the roof or
ground surface to avoid ice build-up around the unit.
• Locate the unit above a load bearing wall or area of the roof that
can adequately support the unit.
• Consult local codes for rooftop applications.
BUILDING STRUCTURE
GROUND
LEVEL
Install unit level or maintain slope tolerance of 2 degrees
( or 2 inches per 5 feet [50 mm per 1.5 m] away from building structure.
FIGURE 29: Outdoor Unit Installation
NOTICE
This system contains both refrigerant and oil. Some rubber roofing
material may absorb oil. This will cause the rubber to swell when it
comes into contact with oil. The rubber will then bubble and could
cause leaks. Protect the roof surface to avoid exposure to refrigerant
and oil during service and installation. Failure to follow this notice
could result in damage to roof surface.
898150-UIM-B-0113