Johnson Controls DHPM09NWM42Q1 Installation Manual
Johnson Controls DHPM09NWM42Q1 Installation Manual

Johnson Controls DHPM09NWM42Q1 Installation Manual

Lx ductless multi zone heat pumps
Hide thumbs Also See for DHPM09NWM42Q1:
Table of Contents

Advertisement

INSTALLATION MANUAL
LX DUCTLESS MULTI ZONE
HEAT PUMPS
MODELS: 16 SEER
1.5 to 3.5 TONS - 1 PHASE
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SHIPPING AND PACKAGING LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
REQUIRED INSTALLATION TOOLS (NOT SUPPLIED) . . . . . . . . . . . . . . . . . .3
SELECTING THE INSTALLATION LOCATION . . . . . . . . . . . . . . . . . . . . . . . . .3
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
REFRIGERANT LINE SET REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . .5
UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
TORQUE REQUIREMENTS FOR CAPS AND FASTNERS . . . . . . . . . . . . . . . .9
INDOOR UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
INDOOR UNIT WIRING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
PIPE FORMING AND DRAIN PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Indoor Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Prevailing Wind Barrier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Clearances for Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Condensate Drainage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Typical System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Outdoor Unit Weights & Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Mounting Bracket Spots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Masonry Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
PVC Wall Sleeve Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Indoor Unit Wall Mounting Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Indoor Electrical Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Drain Piping Outlets Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Proper and Improper Drain Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Left or Right Side Exits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Right or Right Rear Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Left or Left Rear Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Drain Hose Extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Drain Hose Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Pipe Cutting Approved Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Deburring Line Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Flaring Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Proper and Improper Flaring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Connections at Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Flare Nuts Tighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Indoor Unit Attachment to Mounting Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Indoor Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Outdoor Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Multi Zone Matchup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Heat Pump Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Insulation Thickness & Material Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Refrigerant Line Set Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Indoor Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
RETAIN THESE INSTRUCTIONS FOR
FUTURE REFERENCE
SECTION I: GENERAL
These instructions are intended as a general guide and do not super-
sede local codes in any way. Consult authorities having jurisdiction
before installation.
These units must be installed as a matched system as specified in
the UPG Ductless Technical Guide.
Johnson Controls Unitary Products
LIST OF SECTIONS
FLARING WORK AND PIPING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . 12
INDOOR UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
OUTDOOR UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
OUTDOOR UNIT WIRING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
PURGING PROCEDURE, LEAK TEST AND TEST RUN . . . . . . . . . . . . . . . . 18
TEST OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
EMERGENCY OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
HEALTHY FILTER (ACCESSORY) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
TYPICAL UNIT WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
INDOOR AND OUTDOOR UNITS ERROR CODES . . . . . . . . . . . . . . . . . . . . . 24
LIST OF FIGURES
Proper and Improper Drain Hose Installation Application . . . . . . . . . . . . . . . . . 13
Indoor Unit Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Outdoor Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Outdoor Unit Slab or Frame Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
18K Outdoor Unit Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
24K Outdoor Unit Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
30K Outdoor Unit Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
42K Outdoor Unit Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Indoor/Outdoor Piping Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Outdoor Line Set Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Line Set Connection Insulation and Taping . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Utility Bundle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Exterior Wall Utility Cover (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Service Valve Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Air Purging Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Leak Test Line Set Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Emergency Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Filter Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
18K Outdoor Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
24K Outdoor Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
30K Outdoor Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
42K Outdoor Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Indoor Unit Front Panel Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
LIST OF TABLES
Outdoor Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Caps and Fasteners Torque Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Wire Color Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Flare Nut Torque Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Led Status Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
898150-UIM-B-0113

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DHPM09NWM42Q1 and is the answer not in the manual?

Questions and answers

Summary of Contents for Johnson Controls DHPM09NWM42Q1

  • Page 1: Table Of Contents

    These units must be installed as a matched system as specified in avoided may result in minor or moderate injury. It is also used to the UPG Ductless Technical Guide. alert against unsafe practices and hazards involving only property dam- age. Johnson Controls Unitary Products 898150-UIM-B-0113...
  • Page 2: Shipping And Packaging List

    Batteries (AAA) hardware (18 - 24 kBtu systems only) Wall mounting bracket 09, 12 & 18 kBtu (5) Installation Manual screws 24K kBtu (10) Foam tube insulation User’s Information (for condensate line Manual attached to indoor unit) Johnson Controls Unitary Products...
  • Page 3: Required Installation Tools (Not Supplied)

    OUTDOOR UNIT INDOOR UNITS 3. When using the I FEEL feature, select a location for the remote DHMF18CMM42Q1 (2) DHPM09NWM42Q1 control that's about 4 ft. above the floor. (1) DHPM09NWM42Q1 + DHMF18CMM42Q1 (1) DHPM12NWM42Q1 NOTICE (2) DHPM09NWM42Q1 + DHMF24CMM42Q1 (1) DHPM12NWM42Q1 In rooms where inverter type fluorescent lamps are used, the signal from the wireless remote controller may not be received.
  • Page 4: Prevailing Wind Barrier

    14. Install the unit horizontally. INSTALL UNIT AWAY FROM WINDOW DRAIN-WATER HOLE BOTTOM FRAME DRAIN PLUG DRAIN CONNECTOR HOSE (available commerially, inner dia. 0.63”) FIGURE 4: Condensate Drainage FIGURE 3: Clearances for Outdoor Unit Johnson Controls Unitary Products...
  • Page 5: Specifications

    United States, all local codes within the country of origin must be followed. TABLE 4: Heat Pump Electrical Specifications INDOOR UNIT Heat Pumps DHPM09NWM42Q1 DHPM12NWM42Q1 DHPM18NWM42Q1 Power Supply (V, Phase, Hz) 208/230V/1 208/230V/1 208/230V/1/60HZ Min.
  • Page 6: Refrigerant Line Set Requirements

    Note − All outdoor units come from the factory with refrigerant charge to accommodate up to 25 feet (7.5 meters) of lineset. This base charge will accommodate the number of zones that the specific outdoor unit is capable of supporting. Johnson Controls Unitary Products...
  • Page 7: Typical System Components

    42 KBTU OUTDOOR UNIT (TWO TO FIVE ZONES) 30 KBTU OUTDOOR UNIT (TWO TO FOUR ZONES) 24 KBTU OUTDOOR UNIT (TWO TO THREE ZONES) 18 KBTU OUTDOOR UNIT (ONE TO TWO ZONES) FIGURE 5: Typical System Components Johnson Controls Unitary Products...
  • Page 8: Unit Dimensions

    27.5 (699) 148 lbs (67 kg) 38 (965) 16.9 (429) 31.1 (790) 161 lbs (73 kg) 38 (965) 16.9 (429) 31.1 (790) 163 lbs (74 kg) 40 (1016) 14.2 (361) 43.4 (1102) 247 lbs (112 kg) Johnson Controls Unitary Products...
  • Page 9: Torque Requirements For Caps And Fastners

    When the indoor unit is powered from the outdoor unit, a dis- connect switch needs to be installed to power supply circuit between indoor and outdoor units depending on local codes. Johnson Controls Unitary Products...
  • Page 10: Pipe Forming And Drain Piping

    Do not press the refrigerant pipes onto the bottom frame. b. Do not press the refrigerant pipes on the front grille. Johnson Controls Unitary Products...
  • Page 11: Proper And Improper Drain Piping

    4. Put the drain cap into the section to which the drain hose is to be • Once drain water is frozen, the drain hose will be blocked and attached at the rear of the indoor unit. water leakage may result from indoor unit. Johnson Controls Unitary Products...
  • Page 12: Drain Hose Extension

    3. Use a pipe reamer or file to completely remove all burrs from the cut cross section of the pipe. a. Put the end of the copper pipe in a downward direction to avoid having burrs drop in the piping. Johnson Controls Unitary Products...
  • Page 13: Indoor Unit Attachment To Mounting Bracket

    For detaching the indoor unit from the installation plate, pull the indoor unit toward you while pushing the bottom up at the specified places. PUSH PUSH FIGURE 28: Indoor Unit Removal Johnson Controls Unitary Products...
  • Page 14: Outdoor Unit Wiring Connections

    (N)1 of outdoor unit; terminal 2 from indoor unit must go to terminal 2 of outdoor unit; and terminal 3 of indoor unit must go to terminal 3 of outdoor unit. FIGURE 31: 18K Outdoor Unit Terminal Johnson Controls Unitary Products...
  • Page 15: Outdoor Unit Terminal

    (N)1 of outdoor unit; terminal 2 from indoor unit must go to terminal 2 of outdoor unit; and terminal 3 from indoor unit must go to terminal 3 of outdoor unit. MAIN POWER FROM OUTDOOR UNIT DISCONNECT FIGURE 32: 24K Outdoor Unit Terminal Johnson Controls Unitary Products...
  • Page 16: Outdoor Unit Terminal

    Check indoor to outdoor field wiring to confirm (N)1 from indoor goes to (N)1 outdoor, terminal 2 from indoor goes to terminal 2 outdoors and terminal 3 indoors goes to terminal 3 in outdoor. MAIN POWER FROM OUTDOOR UNIT DISCONNECT FIGURE 33: 30K Outdoor Unit Terminal Johnson Controls Unitary Products...
  • Page 17: Outdoor Unit Terminal

    • For connection, first align the union tube and flared refrigerant 1. With torque wrench - Finger tighten and use torque cap per Table line with each other then tighten the flare nuts lightly at first to obtain a smooth match. Johnson Controls Unitary Products...
  • Page 18: Purging Procedure, Leak Test And Test Run

    Figure below provides information on how to access and operate the 2-way angle-type service valve and 2-way shut-off valve. After the piping has been connected to the indoor unit, perform the air purge. FIGURE 37: Line Set Connection Insulation and Taping Johnson Controls Unitary Products...
  • Page 19: Service Valve Operation

    FIGURE 42: Gauge Set Connections for Test Leaks, Evacuation Charging ADDING REFRIGERANT FOR LONGER LINE SET 1. Open the low side manifold gauge valve and weigh in liquid refriger- ant. Use Table 6 to calculate the correct weigh-in charge. 2. Close manifold gauge valves. Johnson Controls Unitary Products...
  • Page 20: Test Operation

    • To stop the unit from operating, press the AUTO/STOP button once and the unit will shut down. The filter must be in place and the front panel must be closed any The code switch can be operated as follows: time the unit is in operation. Johnson Controls Unitary Products...
  • Page 21: Installation And Maintenance Of Healthy Filter (Accessory)

    The outdoor unit wiring diagram is located on the underside of the outdoor unit control access cover. Fig. A Fig. B AIR FILTER HEALTHY FILTER Fig. C FIGURE 45: Filter Replacement Johnson Controls Unitary Products...
  • Page 22: Outdoor Heat Pumps

    898150-UIM-B-0113 FIGURE 46: 18K Outdoor Heat Pumps FIGURE 47: 24K Outdoor Heat Pumps Johnson Controls Unitary Products...
  • Page 23: Outdoor Heat Pumps

    898150-UIM-B-0113 FIGURE 48: 30K Outdoor Heat Pumps FIGURE 49: 42K Outdoor Heat Pumps Johnson Controls Unitary Products...
  • Page 24: Indoor And Outdoor Units Error Codes

    If multiple errors are detected, the display will alternate between each error code. NOTE: No history is kept on past error codes. FIGURE 50: Indoor Unit Front Panel Indicators GREEN LED YELLOW LED RED LED FIGURE 51: Control Board Johnson Controls Unitary Products...
  • Page 25: Error Codes

    • Check for proper clearances around All system functions are terminated except outdoor unit. Low pressure protection indoor fan. • Check outdoor coil for and clean, if necessary. Johnson Controls Unitary Products...
  • Page 26 Indoor ambient sensor (RT1) continue to operate as well as indoor fan. • Check sensor for proper resistance. open or short circuited Unit will not operate in heating mode. • Replace sensor if shorted, open or out-of-calibration. Johnson Controls Unitary Products...
  • Page 27 • Loss of cooling to the heat sink Intelligent Power Module All system functions are terminated except • Low voltage. (IPM) module protection indoor fan. • High ambient temperature • Loose screws fastening the outdoor con- trol to the heat sink Johnson Controls Unitary Products...
  • Page 28 Communication failure between All system functions are terminated except Communication bus will automatically main board and driver board indoor fan. reset and resume normal operation. Outdoor control failure All system functions are terminated. Replace outdoor control. Johnson Controls Unitary Products...
  • Page 29: Led Status Codes

    Compressor desynchronizing ☆ ■ ■ □ Compressor phase-lacking protection □ ☆ ■ □ Compressor phase current detection malfunction ■ ☆ ■ □ Memory chip mistake ☆ ☆ ■ □ DC power supply circuit-short □ □ ☆ □ Johnson Controls Unitary Products...
  • Page 30 Unit D communicationwire misconnection or expansion valve malfunction ■ ■ □ ☆ Subject to change without notice. Published in U.S.A. 898150-UIM-B-0113 Copyright © 2012 by Johnson Controls, Inc. All rights reserved. Supersedes: 898150-UIM-A-1112 York International Corp. 5005 York Drive Norman, OK 73069...