S8FS-G
This Power Supply can be used at an altitude of 3,000 m.
Between 2,000 and 3,000 m, derate the load according to the following derating curve.
15 W, 30 W and 50 W
120
100
80
70
60
40
20
0
0
500
1,000 1,500 2,000 2,500 3,000 3,500
Note: At less than 100 VAC, derate the load at 1.3%/V.
300 W and 600 W
120
100
80
70
60
40
20
0
0
500
1,000 1,500 2,000 2,500 3,000 3,500
Note: At less than 100 VAC, derate the load at 1.3%/V.
16
45 °C max.
100%
50 °C
85%
60 °C
70 °C
55%
25%
Altitude (m)
45 °C max.
100%
50 °C
60 °C
70%
70 °C
40%
10%
Altitude (m)
100 W and 150 W
120
100
80
75
60
50
40
25
20
0
0
500
1,000 1,500 2,000 2,500 3,000 3,500
Note: At less than 100 VAC, derate the load at 1.3%/V.
35 °C max.
100%
40 °C
87.5%
50 °C
60 °C
62.5%
70 °C
37.5%
12.5%
Altitude (m)