Technical Data - Beckhoff KL3222 Documentation

2 channel accurate input terminals for pt100 (rtd)
Hide thumbs Also See for KL3222:
Table of Contents

Advertisement

2.2

Technical data

Technical data
Inputs
Sensor types
Connection technology
Measuring range
Conversion time
Measuring current
Resolution
Measuring accuracy
Bit width in the input process image
Bit width in the output process image
Power supply for the electronics
Current consumption from K-bus
Electrical isolation
Terminal points
Pluggable wiring [} 17]
Weight
Dimensions (W x H x D)
Assembly [} 12]
Permissible ambient temperature range during
operation
Permissible ambient temperature range during
storage
Permissible relative air humidity
Vibration / shock resistance
EMC immunity/emission
Protection class
Installation position
Approval
The KL3222 is designed for 4-wire measurement
The KL3222 is designed for 4-wire measurement. +R/-R are the current-carrying connection cables,
+RL/-RL are the currentless sense cables.
If a sensor is to be connected using 2/3 wire connection technology and the KL3202 cannot be
used, the following applies
• one or two jumper(s) per channel must be set externally, see wiring diagram
• the setting "four-wire" must be retained in R32, the 2/3-wire measurement is not calibrated by the
manufacturer
• the falsifying lead resistance should be entered in R38. The firmware subtracts this lead resis-
tance from the measured resistance in order to determine a corrected temperature. This calcula-
tion of R38 is active in all 3 modes 2/3/4-wire of R32.
KL3222
KL3222, KS3222
2
PT100, PT200, PT500, PT1000, Ni100, Ni120, Ni1000,
resistance measurement (e.g. potentiometer connection, 10
Ω...1,2/5 kΩ), KTY
4-wire (2/3-wire possible, see below)
Pt sensors
-200...+850 °C
Ni sensors
-60...+250 °C
high-precision
-200...+320 °C
approx. 50 ms
typically 0.5 mA
0.01°C per digit
0.1 °C at 40 °C ambient temperature, 4-wire connection,
PT100 sensors and 50 Hz filter
2 data words, 2 status bytes (optional)
2 control bytes (optional)
via the K-bus
typically 60 mA
500 V (K-Bus/signal voltage)
Spring-loaded terminals
for all KSxxxx terminals
approx. 70 g
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
0 °C ... + 55 °C
-25 °C ... + 85 °C
95 %, no condensation
conforms to EN 60068-2-6/EN 60068-2-27, see also
Installation instructions [} 16] for terminals with enhanced
mechanical load capacity
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE, cULus, ATEX [} 22]
Version: 2.3.0
Product overview
11

Advertisement