Quantum Scalar i40 Replacement Manual page 3

Bezel replacement
Hide thumbs Also See for Scalar i40:

Advertisement

Removing the Bezel
3 Shut down the library.
a From the Operator panel, select Actions > Shutdown
b Select Shutdown Library, and Yes to confirm.
c When prompted on the screen, press the power button on the front
panel to OFF. Wait for the Operator screen to turn off and the System
Control Board (SCB) LED to go off.
4 Prepare to gain access to the four (4) bezel screws (see
and
Figure 2
on page 5 for locations).
The method depends upon how your library is installed. Follow the
instructions in the table below that correspond to your library installation.
If your library is...
Installed in a rack high
enough to access to the
bottom bezel screws
Installed in a desktop kit
Installed very low in a rack
so that you cannot access
the bottom bezel screws
unless you remove the
library from the rack
Caution: Only slide the library out far enough to access the two screws
on the bottom of the library. The library is not secured in the
rack or on the desk. Pulling it out too far could cause the library
to slide out of the rack or off the desk.
Caution: Ensure that there is enough slack in the power cords and cables
connected in the rear of the library so that you do not dislodge
them when you slide the library forward.
Quantum Scalar i40 and Scalar i80: Bezel Replacement
Follow these steps...
Unscrew all the thumbscrews that secure the
library to the rack (the Scalar i40 has two
thumbscrews; the Scalar i80 has four). See
Figure 2
on page 5.
Release the desktop cover by removing two
screws at the rear of the desktop cover, then
slide the desktop cover toward the back of the
library two or three inches.
Remove the library from the rack as follows:
Warning: Two people are required to safely
remove the library from the rack.
1 Unplug the power cords, Ethernet cable, and
tape drive cables from the back of the library.
If there are multiple tape drives, label all the
cables so you can reconnect them properly
later.
2 Remove the magazines and tape drives. Label
them before removing, so you know where to
reinstall them later.
3 Unscrew the captive thumbscrews in the rack
ears that secure the library to the rack.
4 Using two people, slide the library all the way
out of the rack and place it on a level table or
desk about waist high.
6-66553-03 Rev B
February 2014
Figure 1
on page 4
3