Mitsubishi Electric LGF-100GX-E Handbook page 52

Remote controller optional, pre-filter, high efficiency filter
Table of Contents

Advertisement

Temperatures and thermistor resistance table
Temperature
Resistance
( °C )
value ( kΩ )
-30
53.9 -
-20
32.8
-19
31.2
-18
29.8
-17
28.4
-16
27.1
-15
25.8
-14
24.7
-13
23.6
-12
22.5
-11
21.5
-10
20.6
-9
19.7
-8
18.8
Temperature
Resistance
( °C )
value ( kΩ )
-7
18.0
-6
17.2
-5
16.5
-4
15.7
-3
15.1
-2
14.5
-1
13.8
0
13.3
1
12.8
2
12.2
3
11.7
4
11.2
5
10.7
6
10.3
7
10.0
Temperature
Resistance
( °C )
value ( kΩ )
8
9.5
9
9.2
10
8.8
11
8.5
12
8.1
13
7.8
14
7.6
15
7.3
16
7.0
17
6.7
18
6.5
19
6.3
20
6.0
21
5.8
22
5.6
─ 52 ─
Temperature
Resistance
( °C )
value ( kΩ )
23
5.4
24
5.1
25
5.0
26
4.8
27
4.7
28
4.5
29
4.3
30
4.2
31
4.0
32
3.9
33
3.7
34
3.6
35
3.5
36
3.4
37
3.2
Temperature
Resistance
( °C )
value ( kΩ )
38
3.1
39
3.1
40
3.0
41
2.8
42
2.7
43
2.7
44
2.6
45
2.5
46
2.4
47
2.3
48
2.2
49
2.2
50
2.1
90
0 - 0.7