Mitsubishi Electric LGF-100GX-E Handbook page 43

Remote controller optional, pre-filter, high efficiency filter
Table of Contents

Advertisement

LED1
LED2
Error code
( green )
( red )
6801
9
blinks
" CLEANING "
" FILTER "
blinking
" CLEANING "
" CORE "
blinking
" PLEASE
blink-
WAIT " blinking
ing
" HO " blink-
blink-
ing
ing
Lit
Lit
Note: The " LC " characters that are displayed simultaneously with the error code indicate the Lossnay attributes in
the M-NET device.
Error
PZ-60DR-E
When multiple Lossnay units are
communi-
used, the Main/Sub setting has not
cation error
been made for the second unit and
following units.
Multiple transmission cables are
wired using multi core cables.
Transmission cable and power
cable are too close.
Transmission cable is not securely
connected.
The length of the transmission ca-
ble wiring is longer than specifi ed
( longer than 500 m ) .
Filter clean-
It is time to clean the Filters.
ing warning
according to
total hours
of operation
Lossnay
It is time to clean the Lossnay
core clean-
cores.
ing warning
according to
total hours
of operation
( PZ-60DR-E )
System is
LED1 blinks at 1 second intervals
starting
during starting operation ( maxi-
( PZ-60DR-E )
mum of 45 seconds ) .
System is
LED1 blinks at 1 second intervals
starting
during starting operation ( maxi-
( PZ-52SF-E )
mum of 45 seconds ) .
No M-NET
The Lossnay units have not been
connection
set to group setting ( registration ) .
information
" DELAY OPERATION 'ON' " is set
In delay
operation
from PZ-60DR-E.
Delay setting switch ( SW5-1 ) on
the Lossnay circuit board is set to
ON.
Cause
─ 43 ─
Action
Turn off the main power supply and
set the Main/Sub selection switch
( SW1 ) ( fi rst unit to " Main " , second
and following units to " Sub ") .
Using suitable cables, wire the
transmission cables so that they
are separated from one another.
Wire the transmission cable at
least 5 cm away from the power
supply cable.
Check the transmission cable con-
nection.
Check the length of the transmis-
sion cable wiring.
After cleaning the fi lters, press
the " FILTER " button of the remote
controller two times.
After cleaning the Lossnay cores,
press the " FILTER " button of the
remote controller two times.
This is not an error.
This is not an error.
Check the Lossnay address and
confi rm that the group setting has
been made.
This is not an error.
This is not an error.