Mitsubishi Electric LGF-100GX-E Handbook page 20

Remote controller optional, pre-filter, high efficiency filter
Table of Contents

Advertisement

( 6 ) External input/output terminals on the Lossnay circuit board
Located on the Lossnay circuit board are terminals for the external output of the Lossnay operating condition,
and input terminals for external switching of the Lossnay fan speed and ventilation mode.
Output terminals
The function and contact rating of each output terminal are described below.
"Operation monitor" and "Bypass operation monitor" are in common with "Operation monitor with delay func-
tion 1" and "Operation monitor with delay function 2", respectively.
( Switch with the DIP switch (function selection switch) on the Lossnay circuit board. Refer to page 25 and 26. )
Output
Turned ON ( closed ) at time
Malfunction moni-
tor
of Lossnay malfunction.
Turned ON ( closed ) at time
Operation monitor
*3
of Lossnay operation.
This can also be turned ON
( closed ) at time of air sup-
ply fan operation.
Turned ON ( closed ) 10 sec-
Operation monitor
with delay func-
onds after start of air supply
tion 1
fan.
Turned ON ( closed ) at time
Bypass operation
monitor
of bypass ventilation.
Turned ON ( closed ) 10 sec-
Operation
monitor with delay
onds after start of air supply
function 2
fan when outdoor air tem-
perature is -5 °C or lower.
Turned OFF ( open ) when
outdoor air temperature is
15 °C or higher.
*1 Terminal
of TM3 is a common terminal with bypass operation monitor/operation monitor with delay function
2 output
.
*2 Terminal
of TM3 is a common terminal with malfunction monitor output
*3 The operation monitor can also be used as an air supply fan operation monitor with the setting described
below.
< When using PZ-60DR-E >
< When not using PZ-60DR-E >
Input terminals
a. High (Extra High)/Low fan speed switching input
This is used for external switching of the fan speed by means of a commercially available CO
During the input of High ( Extra High ) /Low fan speed selection, PZ-60DR-E displays "Automatic
Operation
Fan Speed" indicator. The set fan speed cannot be changed while "Automatic Fan Speed" is
displayed due to operation restrictions. Other remote controllers and system controllers can
change the fan speed display; however, the fan will remain fixed at the input fan speed selection
of High ( Extra High ) /Low.
When PZ-60DR-E is used in a system of multiple Lossnay units, input of High ( Extra High ) /Low
Multiple
fan speed into the "Main" Lossnay will permit the switching of the fan speed of all Lossnay units
units
within the same group. When PZ-60DR-E is not used, input High/Low fan speed into each
Lossnay unit. In this case, the setting is applied only to the Lossnay units that have received the
High/Low input.
• A remote display adaptor ( PAC-SA88HA-E ) , which is sold separately, is required for the connections.
Output
Function
Terminal
TM3
*1
TM4
TM3
*2
Set "2" for operation monitor output of function selection.
Set the operation monitor output switch on the Lossnay circuit board
( SW5-2 ) to ON. ( This function cannot be used when operation monitor
with delay function 1 has been set. )
─ 20 ─
Signal
Form
Uncharged
240 V AC, 1 A
,
a-contact
24 V DC, 1 A
Uncharged
240 V AC, 2 A
,
a-contact
24 V DC, 2 A
Uncharged
240 V AC, 1 A
,
a-contact
24 V DC, 1 A
Contact Rating
Maximum
Minimum
220 V AC, 100 mA
5 V DC, 100 mA
220 V AC, 100 mA
5 V DC, 100 mA
220 V AC, 100 mA
5 V DC, 100 mA
.
sensor, etc.