Mitsubishi Electric LGF-100GX-E Handbook page 42

Remote controller optional, pre-filter, high efficiency filter
Table of Contents

Advertisement

Checklist of error codes displayed on PZ-60DR-E ( when using M-NET ) , PZ-52SF-E or M-NET controllers, and LED displays (Table2-2 )
Error code LED1
LED2
( green )
( red )
6600
6
blinks
6607
8
6608
blinks
0900
3126
8
blinks
3602
3
blinks
4116
2
blinks
5101
4
blinks
5102
5
blinks
6602
1 to 4
6604
blinks
6603
5
blinks
*1 ACK: Acknowledgement signal from other communicating devices.
Error
Multiple
There is another unit with the same
address error
address setting.
No ACK error
Power is not supplied to Lossnay.
*1
Lossnay address was changed.
No answer
Multiple transmission cables are
error
wired using multi core cables.
( M-NET
commu-
Transmission cable is not securely connected.
nication
The length of the transmission cable
error )
wiring is longer than specifi ed ( long-
er than maximum extension 200 m,
longer than 500 m between ends ) .
Lossnay trial
Trial operation switch on the Lossnay
circuit board ( SW2-1 ) is set to ON.
operation
External
When the TM3
device error
ting switch ( SW5-6 ) is ON, the
following conditions are applied.
• OA temperature is still -10 °C or lower,
60 minutes after the output started
• OA temperature is 15 °C or higher within
15 minutes after the output started
• OA temperature is 70 °C or higher
Damper re-
Damper board operation is not
lated error
correct.
Connectors for the damper unit
are not correctly connected.
The switch ( SW5-10 ) setting is
incorrect.
Fan motor
The Lossnay fan does not stop due
operation
to a breakdown of the fan motor
drive error
operation drive of the circuit board.
Fan motor error
OA thermis-
Connectors for the thermistor are
tor related
not correctly connected.
error
RA thermis-
Connectors for the thermistor are
tor related
not correctly connected.
error
Communication
Controller where an error originally
circuit section
occurred is defective.
error
Lossnay circuit board is defective.
Transmission
Power is supplied to the same
cable error
transmission cable from two or
more power supply units.
The power supply unit is connect-
ed to the TB3 side of the power
supply expansion unit.
The power supply unit is con-
nected to the indoor and outdoor
transmission cables.
Cause
output set-
,
─ 42 ─
Action
Check the addresses of devices in
the system.
Check the power supply to Lossnay.
Check the Lossnay address.
Using suitable cables, wire the
transmission cables so that they
are separated from one another.
Check the transmission cable connection.
Check the length of the transmis-
sion cable wiring. ( See the techni-
cal manual for details about the
regulations. )
Check the trial operation switch.
( Refer to page 25 )
When external devices are con-
nected, check the external devices.
When external devices are not
connected, check the TM3
output setting switch ( SW5-6 ) .
( Refer to page 25 )
Remove the rod, and check whether
the dampers can be moved manually.
Check the connection of the lead wire
connectors and the circuit connectors.
Check that the switch (SW5-10) is
OFF. ( Refer to page 26 )
Check and replace the circuit
board.
Check and replace the fan motor.
Check the connection of the lead
wire connectors and the circuit
connectors.
Check the connection of the lead
wire connectors and the circuit
connectors.
Check the controller where the er-
ror occurred.
Replace the circuit board.
Adjust the wiring of the power sup-
ply unit.
,