*1: To execute the operation lock, the execution operation ( of holding down the "Filter" button and the "ON/OFF"
button simultaneously for 2 seconds ) is required at the normal screen.
To cancel, the same operation is also required.
*2: When using weekly timer and night purge operation, please set clock use to on.
*3: When the simple timer is used, night purge operation will not be possible.
*4: When the contact information display is set at the time of a fault, pressing the "Clear" button of the remote
controller will display the number that was set.
When two remote controllers are used, the following settings are permitted for the "Main" remote controller only.
Intermediate
Major items
items ( Names )
Installation
Supply fan
setting
speed setting
Exhaust fan
speed setting
Power supply/
exhaust when
operation starts
Sub Lossnay
setting
Power supply
ON/OFF/AUTO
Operation moni-
tor output selec-
tion
Exhaust fan speed
selection for cold
region intermittent
operation
( at outdoor air
temperature of
-15 °C or lower )
Night purge set-
ting
Automatic ven-
tilation adjust-
ment pattern
selection
Dot matrix
Selection
display
display
SH: L
H: L
L
SH: L
H: L
L
oFF
on
RC
dIP
oFF
on
AUTo
1
2
oFF
Lo
on
oFF
on
1
2
─ 28 ─
Function
Used at Extra High fan speed/Low fan speed
Used at High fan speed/Low fan speed
( Factory setting )
Fixed at Low fan speed ( Multiple ventilation
mode )
Used at Extra High fan speed/Low fan speed
Used at High fan speed/Low fan speed
( Factory setting )
Fixed at Low fan speed ( Multiple ventilation
mode )
"Power supply/exhaust when operation starts"
is not executed ( Factory setting )
"Power supply/exhaust when operation starts"
is executed ( 30 minutes )
Function settings from the remote controller to
the "Sub" Lossnay is enabled ( Factory setting )
Function settings from the remote controller
to the "Sub" Lossnay is disabled
Lossnay remains stopped when the power
supply is turned on ( Factory setting )
Lossnay starts operating when the power
supply is turned on
Lossnay resumes the same operation mode
(stop or start) before power off
Corresponding to the operation monitor out-
put exhaust fan ( Factory setting )
Corresponding to the operation monitor out-
put air supply fan
Exhaust fan stops
Exhaust fan operates at Low fan speed ( fixed )
Exhaust fan normal operation ( without fan
speed change ) ( Factory setting )
Night purge disabled ( Factory setting )
Night purge enabled
Automatic ventilation normal mode / Night
purge operation condition of outdoor air tem-
perature is 28 °C or higher ( within 24 hours )
( Factory setting )
Automatic ventilation outdoor air cooling pri-
ority mode / Night purge operation condition
of outdoor air temperature is 17 °C or higher
( within 24 hours )
Notes
*5
*6
*7
*8