( 10 ) Setting of function selection switches ( SW1, 2, 5, and 6 )
The associated switches are as listed below.
* This function can also be set from PZ-60DR-E. When the function has been switched from the remote con-
troller later on, the system will operate according to the setting of the remote controller.
Type
Name
SW1
Main/Sub selection switch
SW2
1
Trial operation
2
Pulse input *
3
Power supply/exhaust when
operation starts *
4
SA fan fixed at Low speed *
5
EA fan fixed at Low speed *
6
Power supply ON/OFF *
Note 1
7
Bypass ventilation priority at
Automatic mode *
Temperature condition for
Night purge operation
8
TM4
,
output setting
9
Supply Extra High/High *
10
Exhaust Extra High/High *
SW5 1
Delay setting *
Note 1
2
Operation output monitor *
3
Exhaust fan stop during air
conditioner defrost *
Exhaust fan Low fan speed at
outdoor air temperature of -15
°C or lower *
4
Automatic recovery after
power failure *
Note 1
5
Filter cleaning setting *
Note 1
6
TM3
,
output setting
7
Interlock mode setting *
Note 1
8
Lossnay control mode ( Main/Sub ) switching ( The factory setting is set
to "Main". )
ON : Trial operation mode
OFF: Normal mode ( Factory setting )
ON : At the time of pulse signal input ( Requires a pulse width of 200
ms or greater )
OFF: At the time of level signal and Mr. Slim signal inputs ( Factory setting )
ON : Power supply exhaust mode
OFF: Normal mode ( Factory setting )
ON : Low fan speed fixed
OFF: Normal mode ( Factory setting )
ON : Low fan speed fixed
OFF: Normal mode ( Factory setting )
ON : Available
OFF: Unavailable ( Factory setting )
ON : Automatic ventilation outdoor air cooling priority mode / Night
purge operation condition of outdoor air temperature is 17 °C or
higher ( within 24 hours )
OFF: Automatic ventilation normal mode / Night purge operation con-
dition of outdoor air temperature is 28 °C or higher ( within 24
hours ) ( Factory setting )
ON : Operation monitor output with delay function 1. Refer to ( 3 )
Fan speed control by function setting ( page 13 ) , and ( 6 )
Output terminals ( page 20 ) .
OFF: Operation monitor output based on SW5-2 ( Factory setting )
ON : Air supply fan Extra High fan speed
OFF: Air supply fan High fan speed ( Factory setting )
ON : Air exhaust fan Extra High fan speed
OFF: Air exhaust fan High fan speed ( Factory setting )
ON : Delay operation of 30 minutes
OFF: Normal ( Factory setting )
ON : Operation monitor output correspond to air supply fan
OFF: Operation monitor output with normal operation ( Factory setting )
ON : Both Air exhaust fan and Air supply fan ( Low fan speed ) operation
at outdoor air temperature of -15 °C or lower
OFF: Exhaust fan operation ( Only Air supply fan stopped ) ( Factory set-
ting )
ON : After the recovery, operation at the mode preceding the power
failure
OFF: Stop after the recovery ( Factory setting )
Selection switch for accumulated running time of the filter cleaning dis-
play.
ON : 3,000 hours
OFF: No filter maintenance display ( Factory setting )
ON : Operation monitor output with delay functions 2. Refer to ( 3 )
Fan speed control by function setting ( page 13 ) , and ( 6 )
Output terminals ( page 20 ) .
OFF: Bypass ventilation operation monitor output ( Factory setting )
Effective only at the time of external control input usage.
Refer to ( 5 )
Interlock mode ( page 19 ) .