Mitsubishi Electric LGF-100GX-E Handbook page 24

Remote controller optional, pre-filter, high efficiency filter
Table of Contents

Advertisement

Night Purge mode is active; no operation
No
No
temperature 17°C/28°C
or more (within 24
Temperature monitoring
operation (5 minutes)
temperature > 22°C and
Indoor temperature
- Outdoor temperature
Night Purge operation
(Bypass ventilation)
Finish Night Purge
operation (Stop)
*1: When Lossnay is interlocked with the City Multi indoor units, "Stop of Lossnay during interlocked opera-
tion with the City Multi operating in cooling mode" is another necessary condition in addition to that of
"Detection of an outdoor temperature of 17 °C or 28 °C or higher ( within 24 hours ) ".
( Night Purge operation will be performed when either of these necessary conditions has been satisfi ed. )
1:00 A.M.
Yes
The outdoor temperature (OA) setting can be selected either 17°C or
Outdoor
28°C with the DIP switch (SW2-7) in the Lossnay control box.
Refer to the remote controller installation manual for more information.
hours)
Yes
Indoor
> 5°C
Yes
No
6:00 A.M.
Yes
*1
No
55-minute stop
Night Purge
operating
No