Mitsubishi Electric LGF-100GX-E Handbook page 19

Remote controller optional, pre-filter, high efficiency filter
Table of Contents

Advertisement

Interlock mode
Lossnay can set the following four types of interlock modes for the start/stop signal from the external device.
Interlock
Pulse signal input
mode
ON/OFF
The start/stop condition
interlock
will be reversed each
( Remote
time the pulse signal is
controller
input.
last touch
operation
permitted )
ON interlock
Lossnay will start when
the pulse signal is
input.
Stopping is controlled
by the remote controller.
OFF inter-
Lossnay will stop when
lock
the pulse signal is input.
Starting is controlled by
the remote controller.
External
Same as ON/OFF inter-
input prior-
locked.
ity ON/OFF
interlock
*1: Display of liquid crystal display (LCD) when setting is made by the PZ-60DR-E remote controller
Delay operation
This function delays the starting of Lossnay for 30 minutes with respect to the start signal from the exter-
nal device ( and for 10 to 60 minutes when PZ-41SLB-E is used ) . When the remote controllers other than
PZ-41SLB-E are used, LED1 on the Lossnay circuit board will light during delay operation. Also, when PZ-
60DR-E and PZ-41SLB-E are used, there will be a display of the delay time.
Function settings
( Remote controller func-
Delay operation setting
Normal operation
"oFF"
( Factory setting )
Delay operation setting
Delay operation
"on"
Note that delay operation will be disabled under the following condition
When the start signal from the external device is a pulse signal.
When the system is interlocked with Mr. Slim or City Multi indoor units set to the fan operation mode.
When the system is restarted within 2 hours of Lossnay stop.
When the interlock mode is set to "OFF Interlock".
Other than pulse signal
Lossnay will start with
the operation signal of
the external device, and
Lossnay will stop with
the stop signal.
Lossnay will start with
the start signal of the
external device.
Stopping is controlled
by the remote controller.
Lossnay will stop with
the stop signal of the
external device.
Starting is controlled by
the remote controller.
Same as ON/OFF inter-
locked.
Note that during opera-
tion that started with a
signal from the external
device, stopping by the
remote controller will
not be possible.
PZ-60DR-E
( Delay starting time )
tion selection )
0 minutes
( Factory setting )
10 to 60 minutes ( in
10-minute units )
PZ-60DR-E
input
( Remote controller
function selection ) *1
Interlock mode
setting selection
"onoF"
( Factory setting )
Interlock mode
setting
"on"
Interlock mode
setting
"oFF"
Interlock mode
setting
"oUT"
Setting Method
PZ-41SLB-E
─ 19 ─
Setting Method
PZ-41SLB-E
( Interlock
mode )
1
( Factory
setting )
2
3
4
PZ-52SF-E or remote
controller not used
( Function selection switch )
SW5-1: OFF
( Factory setting )
SW5-1: ON
PZ-52SF-E or remote
controller not used
( Function selec-
tion switch )
SW5-7: OFF
SW5-8: OFF
( Factory setting )
SW5-7: ON
SW5-8: OFF
SW5-7: OFF
SW5-8: ON
SW5-7: ON
SW5-8: ON

Advertisement