With a separate steamer SS20(A), observe that the
temperature sensor must not be installed in the area
affected by steam.
Note! Do not install the temperature sensor closer
than 1000 mm to an omnidirectional air vent or
closer than 500 mm to an air vent directed away
from the sensor. See figure 10. The air flow near an
air vent cools down the sensor, which gives inac-
curate temperature readings to the control unit. As
a result, the heater might overheat.

3.4. Installing the Humidity Sensor

Fasten the humidity sensor on the wall as far from
the heater as possible and at a distance of 500–700
mm from the ceiling. See figures 8 and 9.
WX232
Figure 9.
Abbildung 9.
36
The place of the temperature and humidity sensors in connection with floor-mounted heaters
Position der Temperatur- und Luftfeuchtigkeitsfühler bei freistehende Öfen
DE
Bei einem separaten Verdampfer SS20(A) ist zu
beachten, dass der Temperaturfühler nicht in dem
Bereich angebracht werden darf, der vom Dampf
getroffen wird.
Achtung! Der Temperaturfühler darf nicht näher
als 1000 mm an einen Mehrrichtungs-Luftschlitz
oder näher als 500 mm an einen Luftschlitz an-
gebracht werden, der vom Fühler wegzeigt. Siehe
Abbildung 10. Der Luftzug in der Nähe von Luft-
schlitzen kühlt den Fühler ab, was zu ungenauen
Temperaturmessungen am Steuergerät führt. Dies
kann zu einer Überhitzung des Ofens führen.
3.4. Montage des Feuchtigkeitsfühlers
Bringen Sie den Feuchtigkeitsfühler so weit wie
möglich vom Ofen entfernt an der Wand an, in ei-
nem Abstand von 500–700 mm zur Decke. Siehe
Abb. 8 und 9.
WX232
WX325
Humidity sensor
Feuchtigkeitsfühler
Permitted area for
WX325
Zulässiger Bereich
für WX325
min.
100 mm
max.
200 mm
WX232
WX232
Temperature sensor
Temperaturfühler