3
Configuration
Caution
The CPV Direct contains electronically sensitive compo
nents. The CPV Direct will be damaged if you touch the
contact surfaces of the plug connectors or if you do not
observe the regulations for handling electrostatically
sensitive components.
Proceed with the configuration as follows:
1. Switch off the power supply.
2. Remove the switch cover.
3. Set the following with the DIL switch: the station
number, the device−related diagnosis for PROFIBUS−DP.
4. If modules or valve terminals are connected to the CPI
extension connection: Carry out automatic recognition
(see section 7).
5. Refit the switch cover.
6. If the CPI system is the first or last slave in a field bus
segment, the terminating resistor in the Festo Sub−D
plug must be activated.
Warning
S Check the measures for putting the system into a
safe state in the event of an EMERGENCY STOP.
Further information: manual P.BE−CP−DI02−...