Wiring Diagram - Siemens XDLC Installation Instructions Manual

Class x device loop card
Table of Contents

Advertisement

CLASS A or CLASS X WIRING**
NO T-TAPPING ALLOWED
ZONE 1
INITIATING
DEVICE
*
CC-5
1
2
3
4
ZONE 3
INITIATING
DEVICE
*
CC-5
9
10
11
12
**OPERATES IN FULL CONFORMANCE WITH CLASS A (ULC DCLA)
Figure 4
XDLC Wiring Diagram
Siemens Industry, Inc.
Building Technologies Division
ZONE 2
*
5
6
7
8
ZONE 4
*
13
14
15
16
NOTES:
1. NO END OF LINE DEVICE REQUIRED.
2. ALL CIRCUITS SUPERVISED AND POWER LIMITED PER NEC 760.
3. POSITIVE OR NEGATIVE GROUND FAULT DETECTED AT <50K OHMS ON TERMINALS 1-16.
CLASS B WIRING***
T-TAPPING ALLOWED
ZONE 1-1
INITIATING
DEVICE
*
ZONE 1-2
INITIATING
DEVICE
*
CC-5
1
2
3
4
5
ZONE 3-5
INITIATING
DEVICE
*
ZONE 3-6
INITIATING
DEVICE
*
CC-5
9
10
11
12
13
***OPERATES IN FULL CONFORMANCE WITH CLASS B (ULC DCLB)
5
ZONE 2-3
*
SHIELD (OPTIONAL)
TERMINATE IN ENCLOSURE
WITH THE XDLC. TERMINATE
AT ONE END ONLY.
TERMINATE TO EARTH
GROUND.
ZONE 2-4
*
SHIELD (OPTIONAL)
TERMINATE IN ENCLOSURE
WITH THE XDLC. TERMINATE
AT ONE END ONLY.
TERMINATE TO EARTH
GROUND.
6
7
8
ZONE 4-7
*
SHIELD (OPTIONAL)
TERMINATE IN ENCLOSURE
WITH THE XDLC. TERMINATE
AT ONE END ONLY.
TERMINATE TO EARTH
GROUND.
ZONE 4-8
*
SHIELD (OPTIONAL)
TERMINATE IN ENCLOSURE
WITH THE XDLC. TERMINATE
AT ONE END ONLY.
TERMINATE TO EARTH
GROUND.
14
15
16
A6V101040156_en--_c