Siemens SINAMICS G130 Operating Instructions Manual page 15

Dv/dt filter plus voltage peak limiter
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Table 2- 2
Max. pulse frequency when a dv/dt filter is used in units with a rated pulse frequency of 2 kHz
Order number
Power [kW]
6SL3310-...
1GE32-1AAx
110
1GE32-6AAx
132
1GE33-1AAx
160
1GE33-8AAx
200
1GE35-0AAx
250
Table 2- 3
Max. pulse frequency when a dv/dt filter is used in units with a rated pulse frequency of 1.25 kHz
Order number
Power [kW]
6SL3310-...
1GE36-1AAx
315
1GE37-5AAx
400
1GE38-4AAx
450
1GE41-0AAx
560
1GF31-8AAx
110
1GF32-2AAx
132
1GF32-6AAx
160
1GF33-3AAx
200
1GF34-1AAx
250
1GF34-7AAx
315
1GF35-8AAx
400
1GF37-4AAx
450
1GF38-1AAx
560
1GH28-5AAx
75
1GH31-0AAx
90
1GH31-2AAx
110
1GH31-5AAx
132
1GH31-8AAx
160
1GH32-2AAx
200
1GH32-6AAx
250
1GH33-3AAx
315
1GH34-1AAx
400
1GH34-7AAx
450
1GH35-8AAx
560
1GH37-4AAx
710
1GH38-1AAx
800
dV/dt filter plus Voltage Peak Limiter
Operating Instructions, 03/2012, A5E00692302A
Output current for a
pulse frequency of 2 kHz [A]
Line voltage 380 V – 480 V 3 AC
210
260
310
380
490
Output current for a
pulse frequency of 1.25 kHz [A]
Line voltage 380 V – 480 V 3 AC
605
745
840
985
Line voltage 500 V – 600 V 3 AC
175
215
260
330
410
465
575
735
810
Line voltage 660 V – 690 V 3 AC
85
100
120
150
175
215
260
330
410
465
575
735
810
Max. pulse frequency when a dv/dt filter is used
4 kHz
4 kHz
4 kHz
4 kHz
4 kHz
Max. pulse frequency when a dv/dt filter is used
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
General