Siemens SIMATIC Mobile Panel 277 IWLAN Application Description page 48

Evaluate through which access point the mobile panel communicates, evaluating an access point clients list
Table of Contents

Advertisement

5 Configuration Process
5.2 STEP 7 configuration
No.
"OBJECT_POINTER" parameter:
The "UDT220" has to be used on the
"OBJECT_POINTER" parameter.
In the declaration line of FC15 the
"ObjectPointer_FC220_02" variable was
created in the "Temp folder" for this purpose.
(The parameter is not used any further in the
configuration).
7.
FC15, Evaluation_Scalance_01:
Network 7:
Through network 7 it is checked whether the
second mobile panel is still registered at the
first access point.
If the signal of FC220 "Data_COMPARE"
(DB25.DBX30.0) is not present for more than
250ms, then the second mobile panel is no
longer registered at the first access point.
Background:
(The "Clients list" of the first 10 nodes is read
out subsequently). If a match is found, the
signal is output through the FC220
"Data_COMPARE". The signal is only pending
until a new
"MIB variable" was read in using the FB3.
Note:
The time that is needed to subsequently read
out all 10 nodes may vary.
Depending on the "cycle time" it may be
necessary to increase the specified time of
250ms.
48
Updates
Screens
Evaluating An Access Point Clients List
V1.0, Entry ID: 48946495