3 Technical specifications
Outdoor unit
AWHP 16 MR-2
AWHP 16 TR-2
Tab.3
Indoor unit technical specifications
Specifications
Operating temperature range
Bluetooth frequency band
Bluetooth power
Tab.4
Outdoor unit conditions of use
Limit operating temperatures
Water in heating mode
Outdoor air in heating mode
Water in cooling mode for the non-
insulated models
Water in cooling mode for the insu
lated models
Outdoor air in cooling mode
Tab.5
Heating mode: outdoor air temperature +7 °C, water temperature at the outlet +35 °C. Performances in accordance
with EN 14511-2.
Measurement type Unit
Heat output
kW
Coefficient of Per
formance (COP)
Absorbed electri
kWe
cal power
Nominal water flow
3
m
/hour
rate (ΔT = 5 K)
12
AWHP MIV-S
3.2.2
The specifications are valid for a new appliance with clean heat
exchangers.
Maximum operating pressure: 0.3 MPa (3 bar)
AWHP 4.5 MR
AWHP 6 MR-3
+18 °C/+55 °C
+18 °C/+60 °C
-15 °C/+35 °C
-15 °C/+35 °C
+18 °C/+25 °C
+18 °C/+25 °C
+7 °C / +25 °C
+7 °C / +25 °C
+7 °C/+46 °C
+7 °C/+46 °C
AWHP 4.5
AWHP 6
MR
MR-3
4.60
5.82
5.11
4.22
0.90
1.38
0.88
1.00
Associated/compatible indoor units
MIV-S 11-16/EM
MIV-S 11-16/EMI
MIV-S 11-16/ET
MIV-S 11-16/ETI
MIV-S 11-16/H
MIV-S 11-16/HI
MIV-S 11-16/EM
MIV-S 11-16/EMI
MIV-S 11-16/ET
MIV-S 11-16/ETI
MIV-S 11-16/H
MIV-S 11-16/HI
Heat pump
AWHP MIV-S
+7 °C to +30 °C
2400 – 2483.5 MHz
+5 dBm
AWHP 8 MR-2
+18 °C/+60 °C
-20 °C/+35 °C
+18 °C/+25 °C
+7 °C / +25 °C
+7 °C/+46 °C
AWHP 8
AWHP 11
MR-2
MR-2
7.9
11.39
4.34
4.65
1.82
2.45
1.53
1.96
AWHP 11 MR-2
AWHP 16 MR-2
AWHP 11 TR-2
AWHP 16 TR-2
+18 °C/+60 °C
+18 °C/+60 °C
-20 °C/+35 °C
-20 °C/+35 °C
+18 °C/+25 °C
+18 °C/+25 °C
+7 °C / +25 °C
+7 °C / +25 °C
+7 °C/+46 °C
+7 °C/+46 °C
AWHP 11
AWHP 16
TR-2
MR-2
11.39
14.65
4.65
4.22
2.45
3.47
1.96
2.53
7748711 - v03 - 08062020
AWHP 16
TR-2
14.65
4.22
3.47
2.53