OPERATION MENU
Upon power up of the control, using the
advance key will scroll through the various
prompts found in the Operations Menu.
At any point within the Operations menu
to return to the default display push the
Infinity ˆ key.

Operations Menu

[````] PAr1
[````] PAr2
[`AUt] Autotune
[`C; M ] Control Mode
[`h; p b] Heat Proportional Band
[`C; p b] Cool Proportional Band
[``ti] Time Integral
[``td] Time Derivative
[o; t b1] Time Base
[o; t b2] Time Base
[`A; l o] Alarm Low Set Point
[`A; h i] Alarm High Set Point
[`i; C a] Calibration Offset
[btth] Bluetooth
PM3/PM6 LEGACY™ Express PID Controller • 18 •
Display
Parameter Name Description
Autotune
[`AUt]
[ AUt]
Start an autotune. While active the
upper or left and lower or right dis-
play will flash [tUn1] and [Attn].
Appears if: Heat or cool algorithm
set to PID
Range: Defaults are shown below
in bold
[``no] No
[`yES] Yes
Control Mode Active
[`C; M ]
View the current control mode.
[ C.M]
Appears if: Always
Range: (Defaults are shown in bold)
[`off] Off
[AUto] Auto
[MAn] Manual
Heat Proportional Band
[`h; P b]
Set the PID proportional band for the
[ h.Pb]
heat outputs.
Appears if: Heat algorithm set to PID
Range: (Defaults are shown in bold)
0 to 9,999.000°F or units
0 to 5,555.000°C
Units, 25.0°F or 14.0°C
Cool Proportional Band
[`C; P b]
Set the PID proportional band for the
[ C.Pb]
cool outputs.
Appears if: Cool algorithm set to PID-
Range (Defaults are shown in bold)
0 to 9,999.000°F or units
0 to 5,555.000°C
Units, 25.0°F or 14.0°C