D64RP14 SERIES A2 DIGITAL GROUND FAULT RELAY
GROUND FAULT TEST – D64RP14
Double clicking the remote button connected to terminals R1 and R2 invokes a relay
test. A simulated current equal to 1.2 times the trip current set on the Trip Level
DIPswitches replaces the measured current. After the trip delay time set on the Trip
Delay DIPswitch has elapsed, the unit should trip and the green IND LED should fast
blink. This procedure tests the functionality of the unit.
RESETTING THE D64RP14 AFTER GROUND FAULT TRIP TEST
If the D64RP14 is in the Non-failsafe or Failsafe mode (manual reset), press the remote
RESET button to reset the relay.
If the D64RP14 is in the Pulsed Trip Auto Reset mode it will reset automatically after 3
seconds.
This form provides spaces to record the date the test was performed and the results. Those in
charge of the building's electrical installation should retain the form in order to be available to
the authority having jurisdiction.