Eaton Cutler-Hammer D64RP14 Series Instruction Manual page 12

A2 digital ground fault relay
Table of Contents

Advertisement

D64RP14 SERIES A2 DIGITAL GROUND FAULT RELAY
Ground Fault Trip Time Delay.........................................................................0.5 –10.0 seconds
Setting within Range ........................................................DIPswitches 4, 5, & 6 on front of relay
Accuracy:
Has a current dependent behavior:
If set for
0.5 sec
1.0 sec
1.5 sec
2.0 sec
2.5 sec
5.0 sec
7.5 sec
10.0 sec
Frequency Response Range ..............................................................................................45 - 65 Hz
Thermal Characteristics:
Short Time Withstand:
1000A..................................................................................................................... 1 second
2000A.................................................................................................................. 0.1 second
Environment:
Operating Temperature........................................................................................ -35
Storage ................................................................................................................ -40
Humidity .................................................................................................85% (No Condensation)
Shock resistance ..................................................................................................... 10G (no malfunction)
Vibration resistance ....................................10G, 10-55 Hz at 1.5 mm double amplitude (no malfunction)
Ingress protection ...............................................................................................................................IP20
Dimensions (refer to Figure 3):
Height.....................................................................................................................1.77" (45 mm)
Width......................................................................................................................2.76" (70 mm)
Depth (not including terminal blocks)................................................................4.03" (102.4 mm)
Depth (including terminal blocks)..................................................................... 4.95" (125.7 mm)
Mounting (refer to Figure 3):
DIN rail .............................................................................................................................. 35 mm
Two Screw .............................................................................................. #8 x 3/4" (M4 x 20 mm)
Weight:
Open ............................................................................................................... 0.88 lbs. (0.40 kg)
Packaged ........................................................................................................ 1.08 lbs. (0.49 kg)
Applicable Standards:
EN 61000-6-3
Revision 1
May, 2005
Delay when current exceeds trip current setting by a factor of
1.2
2
546-579 ms
523-542 ms
1018-1082ms
995-1045 ms
1518-1582 ms
1495-1545 ms
2018-2082 ms
1995-2045 ms
2518-2582 ms
2495-2545 ms
5018-5082 ms
4995-5045 ms
7234-7582 ms
7211-7545 ms
9734-10082 ms
9711-10045 ms
Electromagnetic compatibility (EMC) - Part 6-3 Generic standards–
Emission standard for residential, commercial and light-industrial
environments (note: = lowest levels):
30-230 MHz
30 dBµV at 10m distance
230-1000 MHz
37 dBµV at 10m distance
Page 12
PUB 51079
≥6
4
512-529 ms
506-523 ms
984-1032 ms
978-1026 ms
1484-1532 ms
1478-1526 ms
1984-2032 ms
1978-2026 ms
2484-2532 ms
2478-2526 ms
4984-5032 ms
4978-5026 ms
7200-7532 ms
7194-7526 ms
9700-10032 ms
9694-10026 ms
°
C to +60
°
C
°
C to +80
°
C