Festo CPV GE-ASI Series Brief Description page 14

Valve terminal with as-interface
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 11
4
Installation
Use the Festo cable sockets ASI-SD-FK for connecting the
type 10 valve terminals. You thereby comply with protec-
tion class IP65.
Proceed as follows.
1. Connect the cable socket in accordance with the separ-
ate brief description.
2. Make sure that the AS-interface cable is not stretched.
3. Place the cable socket into position and screw it tight.
1
AS-interface cable
Cable cap type: ASI-
2
KK-FK
3
Cable socket type:
ASI-SD-FK8 (or
ASI-SD-FK180)
Please note the following with branch lines.
The max. total length of the AS-Interface bus: 100 m.
The length of the operating voltage cable depends on
the current consumption of the terminal and on fluctu-
ations in the operating voltage.
An open-ended cable should be fitted with a Festo
cable cap ASI-KK-FK or with a cable bushing ASI-KT-FK.
You therefore avoid leakage currents and comply with
protection class IP65.
14
1
Festo CPV..-GE-ASI-... 0112b English
2
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents