Festo CPV GE-ASI Series Brief Description page 13

Valve terminal with as-interface
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 11
3
Addressing the AS-Interface valve terminal
type 10
3.1 Assign the AS-Interface slave address
We recommend the use of the Festo addresser ASI-PRG-
ADR part no. 18959 with adapter cable part no. 18960 (or
Siemens PSG)
Before connecting an AS-Interface slave to the bus, assign
a non-reserved address to each slave. Set the desired ad-
dress with the AS-Interface addresser. Permitted range
1 ... 31.
Please note:
The factory setting of the terminal is address 00
ID code and IO code see type plate on the terminal
It is not necessary to parametrize the AS-Interface slaves
3.2 Output addresses of the solenoid coils (top view)
Terminal with 2 double valves
2
4
3
1
Festo CPV..-GE-ASI-... 0112b English
Terminal with 4 single valves
1 2 3 4
13