Power Supply - Siemens SIMATIC MICRO-DRIVE PDC1000 Equipment Manual

Servo drive system controller
Hide thumbs Also See for SIMATIC MICRO-DRIVE PDC1000:
Table of Contents

Advertisement

2.3

Power supply

Infeed points
You supply the PDC at the logic unit (1L+, 2L+) and power unit (4L+) infeed points with the
following voltages:
Table 2- 1
Supply voltage of PDC
Infeed points
Nominal supply
voltage
Logic unit
24 V DC
1L+, 2L+
Power unit
24 to 48 V DC
4L+
When energy recovery is activated, a supply voltage above 57.6 V DC is also permitted.
1)
Use a suitable bi-directional supply to ensure that the voltage at 4L+ never exceeds 60 V DC
during operation or under fault conditions.
It is essential that you observe the information on recovery in the section "Energy recovery"
in the System Manual SIMATIC MICRO-DRIVE Drive controller PDC
(https://support.industry.siemens.com/cs/ww/en/view/109774126).
Use separate power supply units to supply the logic unit and the power unit or a filter
between the shared power supply unit and the power supply.
PDC1000(F)
Equipment Manual, 02/2020, A5E48775040-AA
Static supply
voltage
20.4 to 28.8 V
19.2 to 57.6 V
1)
WARNING
Dynamic supply
Maximum voltage
voltage
under fault conditions
(power supply) for
maintaining electrical
and functional safety
18.5 to 30.2 V
Max. 42.4 V
Non-periodic over-
voltage max. 35 V
for max. 500 ms
with a recovery
time of 50 s
18.5 to 59.4 V
Max. 60 V
1)
Product overview
2.3 Power supply
Fusing
Internal fusible link, not
replaceable by user.
Fusing on installation
side necessary for
through-wiring!
Two-pole miniature
circuit breaker
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic micro-drive pdc1000f

Table of Contents