Direct Vent Installation (Mandatory for all Matrix boilers)
Direct Vent installation dictates that the combustion air-inlet must be piped directly to the outdoors using the
methods described in this section and in accordance with the National Fuel Gas Code, ANSI Z223.1 (U.S.) or
CSA B149.1 (Canada) and local requirements.
Combustion Air-inlet Contamination
Be careful not to locate the Air-inlet termination in an area where contaminants can be drawn in and used for
combustion. Combustion air containing dust, debris or air-borne contaminants will drastically increase the
required maintenance and may cause a corrosive reaction in the Heat Exchanger which could result in premature
failure, fire, serious injury, or death. See Table 4-1 for a list of areas to avoid when terminating air-intake piping:
Table 4-1 Corrosive Products and Contaminant Sources
Products to Avoid
Antistatic fabric softeners, bleaches, detergents, cleaners
Perchloroethylene (PCE), hydrocarbon based cleaners
Chemical fertilizer, herbicides/pesticides, dust, methane gas
Paint or varnish removers, cements or glues, sawdust
Water chlorination chemicals (chloride, fluoride)
Solvents, cutting oils, fiberglass, cleaning solvents
Refrigerant charge with CFC or HCFC
Permanent wave solutions
Fixer, hydrochloric acid (muriatic acid), bromide, iodine
Cement powder, crack fill dust, cellulose, fiber based insulation
Flammable Solvents and Plastic Piping
Due to the extremely flammable characteristics of most glues, cements, solvents and primers used in the process
of joining plastic vent and air-inlet pipe, explosive solvent vapors must be evacuated from the vent and air-intake
prior to start-up. Avoid using excess cement or primer that may lead to pooling inside the pipe assembly. Freshly
assembled piping assembly should be allowed to cure for a minimum of 8 hours before applying power to the gas
fired appliance. Refer to Mandatory Pre-commissioning Procedure for Plastic Venting in this section.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this
or any other appliance. Failure to follow instructions may result in serious injury or death.
Flammable Cements and Primers – It is the installers' responsibility to familiarize
themselves with the hazards associated with explosive solvents and to take all precautions
to reduce these risks. Failure to follow these instructions can cause explosions, property
damage, injury or death.
Contaminated Sources to Avoid
Laundry facilities
Dry cleaning facilities
Farms or areas with livestock and manure
Wood working or furniture refinishing shops
Swimming pools, hot tubs
Auto body or metal working shops
Refrigerant repair shops
Beauty shops
Photo labs, chemical / plastics processing plants
Concrete plant or construction site