5. Dimensions shown are for units (evaporator/condenser)
with standard design pressures. The waterside design
pressure is 150 psi (1034 kPa). Consult the factory for
unit dimensions with higher design pressures.
6. Unit vibration isolator pads are provided for field
installation and when fully loaded are 0.25 inches
(6 mm) thick.
7. 3.25-inch (83 mm) diameter lifting holes are provided.
See
Figure 5
for lifting details.
8. The shipping skid adds 4.00 inches (105 mm) to the
overall unit height.

Unit Dimensions and Shipping Weight

Figure 7: Representative WME Dimensional Drawing
Table 1: WME Overall Dimensions
Model
1
Heat Exchanger
E3012 / C2612
WME092*S
WME092*S
E3012 / C3012
E3612 / C3012
WME092*S
E3612 / C3012
WME106*S
E3612 / C3612
WME106*S
WME092*D
E4216 / C3616
WME092*D
E4216 / C4216
E4216 / C4216
WME099*D
E4216 / C4216
WME106*D
E4816 / C4216
WME106*D
NOTE: 1. Unit configuration may be different than illustrated. Refer to certified drawings for specific configuration/dimensions.
2. Unit length represents 2 pass, 150 psi water box configuration with grooved connections.
3. Unit height represents largest configuration possible but does not include height of removable eye bolt.
IOM 1266-2 • MAGNITUDE
VFD #1
L
Dished Waterbox Heads
Length
in. (mm)
170.58 (4332)
173.95 (4418)
175.89 (4467)
174.64 (4435)
226.06 (5742)
231.44 (5878)
MODEL WME CHILLERS
®
9. If main power wiring is brought up through the floor, this
wiring must be outside the envelope of the unit.
10. The unit is shipped with a full operating charge of
refrigerant except with the "Partial Disassembly"
knockdown option.
11. Power landing panel is on top of the cabinet. Multiple
point power will have two separate landing panels as
shown in
12. Units with single point power, 575V, and/or the optional
harmonic filter will require additional panels than shown
in
Figure
VFD #2
Marine Waterbox Heads
2
Length
2
in. (mm)
188.46 (4787)
188.08 (4777)
194.39 (4937)
194.64 (4943)
251.21 (6380)
256.94 (6526)
10
Figure
6.
7.
H
OUT
IN
Width in. (mm)
69.10 (1755)
74.53 (1893)
82.88 (2105)
82.97 (2107)
85.13 (2162)
95.87 (2435)
98.03 (2490)
104.3 (2649)
www.DaikinApplied.com
I
nsTallaTIon
R.75
OUT
IN
W
Height
3
in. (mm)
97.69 (2481)
102.65 (2607)
108.74 (2762)
111.24 (2825)
114.82 (2916)
117.41 (2982)

Hide quick links: