and RideThrough
®
WME chillers have the capability for chillers to restart and
reach full load operation quickly in the event of a power loss.
RapidRestore
– Quickly restores cooling capacity when
®
power is restored after a power failure.
• Compressor Re-Start – Amount of time required for
the chiller to re-start.
• Fast Loading – Amount of time required for the
chiller to reach a certain load condition.
RideThrough
– The ability to maintain operation during
®
a momentary power loss event. When RideThrough
is enabled and a power loss occurs, the compressor
motor maintains rotation and the VFD catches and
re-synchronizes with the spinning rotor. This permits
the chiller to return to its pre-power loss capacity within
seconds of power being restored.
®
Table 9: RapidRestore
and RideThrough
Standard
RapidRestore
Compressor
Compressor
Re-Start
Re-Start
20 sec
60 sec
after power
failure*
*
Requires customer supplied Uninterruptible Power Supply (UPS) to the WME
control panel.
**
After compressor re-start time
*** Time is based on unit operating at AHRI conditions.
RAPID RESTORE OPTION
Figure 23: RapidRestore
WME DUAL POWER
24-40
24N-20
RM
WME SINGLE RR
PE
PE
PE
PE
PE
CMPR1
CMPR1
CMPR2
SCHEM, COMPRESSOR CONTROLLER
SEE DWG 336078103
RAPID RESTORE OPTION APPLICABLE TO THE FOLLOWING PART
IOM 1266-2 • MAGNITUDE
NUMBERS: 33865993X
REV. DATE
DRN
ECO
REV
®
®
Times
®
Fast Loading
RideThrough
to 80% Load
75 sec**
5 sec***
Wiring Diagram
®
20 32
24N-21
24-41
RR
RPS
100-240VAC; 50-60Hz; MIN UPS OUTPUT 240VA; 2A
POWER SOURCE SUPPLIED BY OTHERS
DRAWING 3360781020A01
MODEL WME CHILLERS
®
CHANGES
ADDED LOCAL NOTES OF APPLICABILITY TO RAPID RESTORE AND
Power Panel Short Circuit Current
Ratings
Available short circuit current ratings (SCCR) are shown in
Table 10.
Table 10: Short Circuit Current Ratings
Motor
Code
380V - 480V
M6, M7, 66
and 77
®
380V - 480V
68 and 79
380V - 480V
M8, M9, 88
and 99
NOTE: * 600 amp circuit breaker frame size has a 35 kA
SCCR rating. 800 amp circuit breaker frame size has
a 50 kA SCCR rating.
®
22
Standard
Optional
Voltage
Panel
SCCR
SCCR
35 kA* / 50 kA
65 kA
575V
25 kA
35 kA / 50 kA
N/A
65 kA
575V
25 kA
35 kA / 50 kA
50 kA
65 kA
575V
25 kA
35 kA
www.DaikinApplied.com
I
nsTallaTIon
Optional
High
Ultra High
SCCR
100 kA
N/A
100 kA
N/A
100 kA
65 kA

Hide quick links: