C - Smokestack Connection - JENESIS SHS Series Manual

Table of Contents

Advertisement

c – Smokestack Connection
✓In the production of the smokestack, it is necessary to choose the diameter of the smokestack
according to the fuel to be used.
✓Best possible production of the smokestack is necessary for the release of gas waste, for the burner
to burn in the effectively and for your vapor generator to function with the highest efficiency.
Measurements of Opening of the Smokestack According to Capacities
SHS
SHS
Model
250
350
mm Ø
170
170
✓When connecting the steam generator smokestack outlet to the smokestack, the connection from
the generator to the smokestack must be provided with a 10% slope, which will facilitate the discharge
of the exhaust gas.
ÖRNEK BACA BAGLANTISI
1000 mm
SHS
SHS
SHS
500
750
1000
280
300
350
✓When connecting the smokestack flanges, always use a leakproof and
non-flammable gasket.
✓There must be two ½ "size sleeves on the smokestack. The first one is
required for smokestack gas temperature thermocouple, which provides
value to the smokestack temperature thermostat on the steam
generator electrical control panel, and the other is required to use the
smokestack gas analysis device.
✓The dimensions of a smokestack depend on variables such as smoke
temperature, outside temperature, smokestack load and operating time.
The following formula can be applied for smokestack sizing.
SHS
SHS
SHS
1250
1500
1700
350
400
400
SHS
SHS
SHS
2000
2500
3000
400
450
450
8

Advertisement

Table of Contents
loading