Fault Nb. 3 - High Smokestack Temperature
Description :
The smokestack thermostat on the electrical control panel is used for information on the waste
0
smokestack temperature and for safety purposes. The factory setting is 250
C set value. The fault indicates that the
set value specified in the smokestack temperature thermostat is exceeded and the device increases to the high
smokestack temperature. In general, this fault is caused by the burner combustion settings being distorted or set to
high capacities.
Solution
:
0
* The setpoint of the smokestack temperature thermostat must be checked. The setpoint of 250
C might have been
decreased. The temperature must be reinstated.
* Make sure that there is no structural problem with the smokestack temperature thermostat and the temperature
sensor PT-100.
* Burner combustion settings must be checked.
* The burner capacity should be checked and the device must be operated in accordance with the label values.