Installation, Operating and Maintenance Instructions, Warranty
Jenesis Steam Generators are delivered with one operating instructions folder.
The folder contains the installation instructions, the general operating and maintenance instructions for
the steam generator, the operating instructions for all parts used on the steam generator (burner, pump,
etc.) and the warranty documents.
Steam Generators are water pipe steam generators that produce fast steam due to the small volume of
water in them and that do not have a risk of exploding. They are very sensitive to the water used. The
water to be used must be well filtered and free of limescale ions.
Steam generator consists of the main body (smoke channel), coil(serpentine)e (pressure hull), burner,
electric control panel, feed water pump, separator, condensate tank and smokestack sections.
As seen in the picture, the "coil(serpentine)"
consists of two intertwined spirals. The inlet and
outlet ports of the spiral are shown on the front
cover.
When installing the steam generator, a space equal
to the size of the device must be left on the front
side, in case of removal of the "coil(serpentine)".
Otherwise, the steam generator "coil(serpentine)"
cannot be removed.
The water that is purified by the water softening
device and ready to use in the condensate tank is
pressed in through the coil(serpentine)e inlet port
with feed water pumps. When the burner is
activated, the water in the coil(serpentine)e
evaporates, advances towards the outlet and
reaches the separator. Pressure and temperature
controls are made with the control devices on the
separator and the produced steam is served to the
process by opening the main steam valve.