Fault Nb. 2 - High Vapor Temperature
Description :
Steam generators are devices operated by pressure control. The steam thermostat on the electrical
control panel is used to inform the temperature of the steam going into operation and is used for safety. The steam
temperature increases according to the set operating pressure. Since the steam generator has a standard working
pressure of 10 bars, the corresponding steam temperature (approx. 1900C) has been determined as the setpoint. The
fault indicates that the set temperature is exceeded on the steam temperature thermostat and that the device has
switched to superheated steam. Generally, it is caused by not feeding the required amount of water into the device.
Çözümü
:
* The setpoint of the steam temperature thermostat must be checked. The setpoint of 190
decreased. The temperature must be reinstated.
* Make sure that there is no structural problem with the steam temperature thermostat and the temperature sensor
PT-100.
* After all these checks have been carried out, the structures must be manually charged and the burner must be
commissioned after it is seen that water is coming from the first start valve (bypass).
Condensate Tank Water Level Indicator
The condensate tank
should be checked for
water. If there is no water
in the condensate tank,
the device must be
operated after checking
the reason and filling the
tank.
0
C might have been
Check that the supply
valve on the pump
supply line is open.