Chapter 2 - Installation
In This Chapter
2.1 Installing the IEC 62591 Module
Revised October-2019
IEC 62591 Wireless Interface Instruction Manual (for ControlWave Micro)
2.1
Installing the IEC 62591 Module ...................................................... 2-1
2.2
2.3
2.4
2.5
This chapter describes installing the IEC 62591 module in a
ControlWave Micro, installing the Field Link, and connecting the Field
Link to the IEC 62591 Wireless Interface module.
: This chapter covers the physical installation process. To
Note
configure and commission the IEC 62591 Wireless Interface,
refer to Chapter 3, Configuring and Commissioning.
You install the IEC 62591 Wireless Interface module in the
ControlWave Micro as you would any other module. However, you can
install only one IEC 62591 module.
Notes:
▪ Only ControlWave Micro's with 05.50 (or newer) system firmware
support the IEC 62591 module. Version 5.70 (or newer) system
firmware is required for discrete control.
▪ Version 05.80 (or newer) system firmware is required with IEC
Module Firmware V1.20 or later to support new Burst and Event
parameters.
▪ You can install the IEC 62591 module in any I/O slot (slot 3 or
higher except for the last slot in any chassis/housing) in the
ControlWave Micro. You cannot use the IEC 62591 with the
ControlWave Micro Distributed I/O System.
1.
Disconnect power from the ControlWave Micro.
2.
Choose an open I/O slot (except for the last slot of any housing).
3.
Locate the built-in guides on the top and bottom of the housing.
Gently slide the IEC 62591 module into the housing until it seats
4.
into the connectors on the interior back of the housing.
Installation