Addresses; Number Of Elements; List Of Services - Omron E5CN Manual

Digital temperature controller with 11-segment display
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

■ Addresses

■ Number of Elements

■ List of Services

The following table summarizes setup areas 0 and 1.
Area
Setup area 0
This area groups together the protect, manual control, opera-
tion, and adjustment levels.
Setup area 1
This area groups together the initial setting, communications
setting, advanced function setting, and calibration levels.
The variable type is converted to 2-byte ASCII and loaded to the frame.
The following table shows the available variable types.
Variable type
C0
Double-word data. R/O (read only) parameter for setup
area 0.
C1
Double-word data. R/W parameter for setup area 0.
C3
Double-word data. R/W parameter for setup area 1.
* Setup area 1 has no read-only parameters, so there is no variable
type "C2."
An address is appended to each of the variable types. Express
addresses in 2-byte hexadecimal and append them for the specified
access size.
The number of elements is expressed in 2-byte hexadecimal. Specify
the number of elements within the range "0 to 2."
For example, when the number of elements is "0002," this specifies two
items of data from the address.
MRC
SRC
Name of service
01
01
Read Variable Area
01
02
Write Variable Area
05
03
Read Controller
Attributes
06
01
Read Controller Sta-
tus
08
01
Echoback Test
30
05
Operation Com-
mand
2.2 Structure of Command Text
Description
Description
Processing
This service reads from variable areas.
This service writes to variable areas.
This service reads the model number
and communications buffer size.
This service reads the operating sta-
tus.
This service performs an echoback
test.
This service performs operations such
as executing/stopping AT (auto-tuning)
and moving to Setup Area 1.
2-7