Connecting Biometric Readers In Same Rs485 Line With The Cv-350 Controllers; Connecting Biometric Readers When All The Controllers Have Tcp/Ip Communication - CAMDEN CV-940-20 Series Installation Instructions Manual

Biometric keypad reader
Table of Contents

Advertisement

5.1 Connecting Biometric Readers In Same RS485 Line with the CV-350 Controllers

RS485 termination
TCP/IP
50 ohm
• The Biometric readers are connected through RS485
bus. The same RS485 bus that the CV-350 controllers
are connected to.
• Maximum units in one network (CV-350 + Biometric
readers) is 32.
• If there are more than 32 units in one network, please
utilize RS 485 HUB to connect.
• The RS485 Line should be configured in the form of a
daisy chain, NOT in a form of a star. If star must be
used in some points, keep the stubs from the RS485
backbone as short as possible. Maximum length of
the stub is dependant of the installation (total number
of devices in RS485 line (total cable length,
5.2 Connecting Biometric Readers When All The Controllers Have
TCP/IP Communication
• When all the controllers are connected via TCP/IP, then
the RS485 network becomes local (from Reader 1 to
the Controller then to the Reader 2).
• Connect the readers directly to the Rs485 terminals in
each controller.
Jumper for
gnd
Stub
max. 5m
TCP/IP
Switch
50m
max.
1 km max / 32 Units (CV-350 + Biometric Readers)
RS485
termination, cable type...) so recommendation is to
keep stubs shorter than 5 meters, keeping in mind that
this can be possible reason for errors in communication
with PC software
• The cable must be twisted and shielded with a
min. 0.01" in (0.2 mm) 2 cross section.
• Connect the ground (0V) of each unit in the RS 485
Line using a third wire in the same cable.
• The shield of the communication cable between two
devices must be connected to the EARTH from ONE
side of the RS485 Line.
• Use the side that has earth connection to the building's
grounding network.
50m
max.
• If the distance Reader-Controller is high (50 meters)
and if the communication with the reader can not be
established, then terminate the RS485 network by
closing the jumper in the CV-350 Controller or as
described in chapter 4.
Page 6 of 21
CV-940-20 Series
Jumper for
RS485 termination
gnd
50 ohm
50m
max.

Advertisement

Table of Contents
loading

Table of Contents