Procedure
1.
Remove the transformer cover (13) from the
transformer turret (11).
2.
Install the winding cables to the bottom contact.
3.
Install the end shield:
1.
Push the end shield carefully against the
pressing ring (17), until the springs are fully
compressed.
2.
Turn the end shield approximately 20°, to its
locked position.
End of instruction
Installation and maintenance guide
1ZSC000563-AAB EN, REV. 6, 2019-09-12
CAUTION!
Make sure that there is no tension in
the winding cables. Tension in the
winding cables will cause damage to
the bottom contact.
Torque
68 ±6 Nm