5.
Remove the bolts and washers.
6.
Hold the pull-through cord (12) in tension, while
lifting the bushing from the transformer.
7.
Disassemble the draw rod at the lower joint (8).
Use the key grip on the lower draw rod.
58
CAUTION!
Do not damage the stud bolts, there is
a risk of metal falling into the
transformer.
DANGER!
Make sure that the upper draw rod
does not fall down when the lower
joint (8) is disassembled.
CAUTION!
Do not disassemble the joint (7), this
increases the risk of incorrect
assembly.
The joint (7) is locked with
tread-locking fluid grade 42.