ABB industrial drives
Description
Cabinet Options for ACS800-07/U7/17/37

Advertisement

Table of Contents
loading

Summary of Contents for ABB ACS800-07

  • Page 1 ABB industrial drives Description Cabinet Options for ACS800-07/U7/17/37...
  • Page 2: Table Of Contents

    Options covered in this manual Code Description Page Code Description Page B053 IP22 degree of protection G317 Busbar supply terminals B054 IP42 degree of protection G330 Halogen-free materials and wiring B055 IP54 degree of protection G338 Additional wire markings B059 IP54R degree of protection G339 C121...
  • Page 3 Cabinet Options for ACS800-07/U7/17/37 Description 3AUA0000053130 Rev A EN EFFECTIVE: 27.3.2009 © 2009 ABB Oy. All Rights Reserved.
  • Page 5 Table of contents Options covered in this manual ........... . . 2 Table of contents Introduction to the manual What this chapter contains .
  • Page 6 ACS800-07/U7 frames R5 to R8 ........
  • Page 7 I/O options (L) I/O extension and interface modules (+L500, +L501, …) ....... . 33 Additional terminal block X2 (+L504) .
  • Page 8 Table of contents...
  • Page 9: Introduction To The Manual

    Ignoring the instructions can cause physical injury or death, or damage to the equipment. Target audience The manual is intended for ABB sales and sales support personnel and drive application engineers. Purpose of the manual The purpose of the manual is to introduce cabinet options which have not their own manuals or are not described in the hardware manual or technical catalog.
  • Page 10: Contents

    Contents The manual lists the standard cabinet features of different drive types and describes the available options in alphabetic order. Introduction to the manual...
  • Page 11: Standard Features

    Drive type Frames Features when no options are selected ACS800-07 R5, R6, R7, R8 IP21 (UL type 1), main switch fuse with aR fuses, 230 V AC control voltage, control panel CDP312R, no EMC filter, standard control program, bottom entry and exit of...
  • Page 12 More information: ACS800 Ordering Information (3AFE64556568) Standard features...
  • Page 13: Degree Of Protection (B)

    Degree of protection (B) General The degree of protection of the standard cabinet is IP21. The air outlet at the top of the cabinet is covered with a brass grating. With doors open, the degree of protection of the standard cabinet and all cabinet options is IP20. The live parts inside the cabinet are protected against contact with clear plastic shrouds or metallic gratings.
  • Page 14: Definitions

    This option provides the degree of protection of IP22 (UL type 1). It adds plastic gratings and fabric filter mats on the standard cabinet air inlet gratings. ACS800-07 frames R7 and R8: The option contains an additional fan. IP42 (B054) This option provides the degree of protection of IP42 (UL type 2).
  • Page 15: Ip54R (B059)

    The collar is located on the cabinet roof either directly or on the extra fan housing (ACS800-07 frames R7 and R8). The option equips the cabinet air inlets with filter housings containing folded board air filter mats between the inner metallic grating and the outer plastic grating.
  • Page 16: Marine Construction

    Construction (C) Marine construction (C121) The option includes the following accessories and features: • reinforced mechanics • grab railings • door flush bolt which allows the door to open 90 degrees and prevents it from slamming close • self-extinctive materials •...
  • Page 17: Csa Approved (C134)

    CSA approved (C134) The option includes the following accessories and features: • US/CSA type main switch fuse • bottom entry and exit of cables • US cable conduit entry (plain plate without ready-made holes) • 115 VAC control voltage when needed •...
  • Page 18: Brake Choppers

    The option contains brake chopper(s) for feeding braking energy to brake resistors to be dissipated there. The customer must connect brake resistors to the drive. ACS800-07/U7 frames R5 to R8: The brake choppers are located inside the drive module. Standard option for ACS800-07 frame 2×R8i and ACS800-37 frames up to 2×R8i.
  • Page 19: Filters (E)

    EMC filter (E200) This option provides electromagnetic compatibility for drives of category 3 in TN (grounded) systems. Option for ACS800-07 frame R5 and ACS800-U7/17/37 frame R6. Not available for • ACS800-07 frames R6 to R8 and n×R8i • ACS800-U7 frames R6 to R8 •...
  • Page 20: Du/Dt Filter

    ACS800-07/U7 frames R7 and R8: The option adds the cabinet width. ACS800-17/37 frames R7i and R8i: Requires +H359. ACS800-07/U7/17/37 frames R5 to R8, R7i, R8i: Not available for 690 V units. ACS800-07 frames n×R8i: Available only for -0610-3 and -0760-5 equipped with 6- pulse supply.
  • Page 21: Common Mode Filter

    The common mode filter contains ferrite rings mounted around the drive DC busbars. The filter protects the motor bearings by reducing the bearing currents. ACS800-07 and ACS800-U7: Not available for frames R5 and R6 except 0135-3, 0165-3, 0205-3, 0165-5, 0205-5, 0255-5, 0145-7, 0175-7 and 0205-7.
  • Page 22: Line Options (F)

    The supply modules are equipped with a main switch but the cabinet does not contain AC fuses. The customer must install external fuses for the drive. Drive Supply module Main switch Related options: +F260 (aR line fuses) and +F253 (load-switch) More information: ACS800-07 Hardware Manual (3AFE64731165 [English]) Line options (F)
  • Page 23: Acs800-17 And Acs800-37 Frames R6, R7I And R8I

    ACS800-17 and ACS800-37 frames R6, R7i and R8i Standard features The cabinet is equipped with a switch fuse type of main switch which contains ultra- rapid semiconductor fuses (Class aR), and with a line contactor. Drive Main switch +F250 * Control * optional in frame R6, standard in frames R7i and R8i More information: Hardware manual...
  • Page 24: Line Contactor

    More information: Hardware manual, ACS800 Safety Options Hardware Manual (3AFE68578027[English]). gG line fuses (F251) The option replaces the aR AC fuses with gG fuses. See the hardware manual in which cases gG fuses are allowed. Available only for ACS800-07 frames R5 to R8. Line options (F)
  • Page 25: Ar Line Fuses (F260)

    Standard for ACS800-07 frames R5 to R8 and for ACS800-17/37 frames n×R8i. Option for ACS800-07 frames n×R8i. Required with +F253 and +F255. Load-switch (F253) This option provides a load switch for ACS800-07 frames n×R8i. With the option, the supply modules are not equipped with internal load switches. Drive Supply...
  • Page 26: Air Circuit Breaker

    Other required options: +F260. Related options: +F259 and emergency stop functions +Q951, Q951, see page 39. Not available for ACS800-07 frames R5 to R8 and other than 6-pulse n×R8i units. Not available with frame size 1×D4 + n×R8i as standard option.
  • Page 27: Grounding Switch

    Option Option for frames n×R8i 1) The customer must take care of the protection according to the instructions given in ACS800-07 Hardware Manual (3AFE64731165 [English]) 2) With load switch option, the internal main switch is removed from the supply module 3) Frames n×R8i are equipped with an air circuit breaker as standard.
  • Page 28: G300 Cabinet Heater (External Supply)

    The power output of the semiconductor-type heating elements depends on the environmental temperature. ACS800-07 frames R5 to R8: The customer must switch the heating off when it is not needed by cutting the supply voltage off. ACS800-07 frames n×R8i, ACS800-17 and ACS800-37: The drive switches the heating off when it is running.
  • Page 29: 115 V Ac Control Voltage

    Terminals for external control voltage (G307) The option provides terminals for connecting external control voltage. Note: The external control voltage is not supplied to the fans and, in ACS800-07 frames n×R8i, to the Diode Supply System Board (DSSB). Output for motor heater (G313)
  • Page 30: Busbar Supply Terminals

    Busbar supply terminals (G317) The option provides input busbar terminals that are suitable for connecting busbar trunking systems. The option is available only for ACS800-07/17/37 frames n×R8i. Other required options: +F253 or F255. Halogen-free materials and wiring (G330) The option provides halogen-free cable ducts, control wires and wire sleeves, thus reducing toxic fire gases.
  • Page 31 Option Additional markings Wire code G340 Equipment pin numbers are marked with rings on wires between modules and on wires connected to equipment, terminal blocks and detachable screw terminals. Main circuit conductors are marked. G341 Equipment identifications and terminal block pin numbers are marked by K1 24 rings on optical fibres, on wires between modules, and on wires...
  • Page 32: Top Entry

    Common motor terminal cubicle (H359) The option provides an additional cubicle which contains terminals for motor output (top or bottom exit) and ball-stud terminals for temporary grounding. Not available for ACS800-07 frames R5 to R8, ACS800-U7, ACS800-17 and ACS800-37. Cabling (H)
  • Page 33: Thermistor Relays (1 Or 2 Pcs)

    I/O options (L) I/O extension and interface modules (+L500, +L501, …) Analog and digital I/O extension modules and encoder and resolver interface modules are inserted in the optional module slots on the drive control unit. More information: See the user’s manuals of the options. Additional terminal block X2 (+L504) Description The standard terminal blocks of the drive I/O board are wired to the additional...
  • Page 34: Pt100 Relays (3, 5 Or 8 Pcs)

    The thermistor relay provides terminals for the measuring circuit (series-connected the PTC thermistors) and terminals of one normally open contact. The relay can be reset by pressing its reset button or the resetting can be wired externally. The customer connects PTC sensors to the thermistor relay and the terminals of the auxiliary relay of the normally open contact, for example, to •...
  • Page 35: Description

    Description The Pt100 relay is used for the overtemperature supervision of motors equipped with Pt100 sensors. For example, three sensors measure the temperature of the motor windings and two sensors the temperature of the bearings. The sensor resistance increases linearly as the temperature rises. The Pt100 relay releases at an adjustable wake-up level and indicates motor overtemperature through its change- over contact.
  • Page 36: Atex Certified Thermal Protection With Ptc (+L513)

    The operating temperatures of the relay are recommended to be set, typically for example, as follows: • 120…140 °C when only tripping is in use • alarm 120…140 °C and trip 130…150 °C when both alarm and trip are used. ATEX certified thermal protection with PTC (+L513) The option contains an ATEX certified thermistor relay.
  • Page 37: Starter For Auxiliary Motor Fan

    The drive controls the auxiliary motor fan on when the drive is running the motor and off when not. ACS800-07 frames R5 to R8: The customer can control the starter on and off also externally by wiring the input to terminal block X6.
  • Page 38: Trip Limit Setting Ranges

    Trip limit setting ranges Option Manual motor starter trip limit setting code range M600 1…1.6 A M601 1.6…2.5 A M602 2.5…4 A M603 4…6.3 A M604 6.3…10 A M605 10…16 A M605 16…25 A Starter for auxiliary motor fan (M)
  • Page 39: Safety Features (Q)

    Safety features (Q) See ACS800 Safety Options Hardware Manual (3AFE68578027[English]) for the following safety options. Option Function Notes code Q950 Prevention of Unexpected Start Q951 Category 0 emergency stop In frames R5 to R8, also option +F250 is required. Q952 Category 1 emergency stop In frames n×R8i, also options +F255 and +F260 are required.
  • Page 40 Safety features (Q)
  • Page 42 ABB Oy ABB Inc. ABB Beijing Drive Systems Co. Ltd. AC Drives Automation Technologies No. 1, Block D, A-10 Jiuxianqiao Beilu P.O. Box 184 Drives & Motors Chaoyang District FI-00381 HELSINKI 16250 West Glendale Drive Beijing, P.R. China, 100015 FINLAND...

This manual is also suitable for:

Acs800-u7Acs800-17Acs800-37

Table of Contents