Measurement Ranges Of The Analog Inputs For Voltage - Siemens SIMATIC S7 System Manual

Hide thumbs Also See for SIMATIC S7:
Table of Contents

Advertisement

553BTechnical specifications
A.3 CPU 1212C
A.3.3.3

Measurement ranges of the analog inputs for voltage

Table A- 36
Analog input representation for voltage
System
Decimal
Hexadecimal
32767
7FFF
32512
7F00
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-20736
AF00
-27648
9400
-27649
93FF
-32512
8100
-32513
80FF
-32768
8000
678
±10 V
±5 V
11.851 V
5.926 V
11.759 V
5.879 V
10 V
5 V
7.5 V
3.75 V
361.7 μV
180.8 μV
0 V
0 V
-7.5 V
-3.75 V
-10 V
-5 V
-11.759 V
-5.879 V
-11.851 V
-5.926 V
Voltage Measuring Range
±2.5 V
2.963 V
Overflow
2.940 V
Overshoot range
2.5 V
Rated range
1.875 V
90.4 μV
0 V
-1.875 V
-2.5 V
Undershoot range
-2.940 V
Underflow
-2.963 V
0 to 10 V
11.851 V
Overflow
11.759 V
Overshoot
range
10 V
Rated range
7.5 V
361.7 μV
0 V
Negative
values are not
supported
S7-1200 Programmable controller
System Manual, 11/2011, A5E02486680-05

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1200

Table of Contents