A.10.2.1
CP 1242-7
Table A- 152 Technical specifications of the CP 1242-7
Technical specifications
Order number
Wireless interface
Antenna connector
Nominal impedance
Wireless connection
Maximum transmit power
GPRS
SMS
Permitted ambient conditions
Ambient temperature
during storage
during transportation
during operation with a vertical installation (DIN rail
horizontal)
during operation with a horizontal installation (DIN rail
vertical)
Relative humidity at 25 °C during operation, without
condensation, maximum
Degree of protection
Power supply, current consumption and power loss
Type of power supply
Power supply / external
minimum
maximum
Current consumption (typical)
from 24 V DC
from the S7-1200 backplane bus
Effective power loss (typical)
from 24 V DC
from the S7-1200 backplane bus
S7-1200 Programmable controller
System Manual, 11/2011, A5E02486680-05
6GK7 242-7KX30-0XE0
SMA socket
50 ohms
GSM 850, class 4: +33 dBm ±2dBm
GSM 900, class 4: +33 dBm ±2dBm
GSM 1800, class 1: +30 dBm ±2dBm
GSM 1900, class 1: +30 dBm ±2dBm
Multislot class 10
device class B
coding scheme 1...4 (GMSK)
Mode outgoing: MO
service: point-to-point
-40 °C to 70 °C
-40 °C to 70 °C
0 °C to 55 °C
0 °C to 45 °C
95 %
IP20
DC
24 V
19.2 V
28.8 V
100 mA
0 mA
2.4 W
0 W