Table 9- 64
Example 1 - If the parameterized velocity is reached and maintained
JogForward
The task is started with a positive edge at the input parameter "JogForward" or "JogBackward".
While the task is active, the output parameter "Busy" indicates the value TRUE.
When the parameterized velocity is reached, the output parameter "InVelocity" changes to TRUE.
When the input parameter "JogForward" or "JogBackward" is reset to the value FALSE, the axis motion ends. The axis
starts to decelerate. As a result, the axis no longer moves at constant velocity and the output parameter "InVelocity"
changes its status to FALSE.
If the axis has come to a standstill, the motion control task is complete and the output parameter "Busy" changes its
value to FALSE.
S7-1200 Programmable controller
System Manual, 11/2011, A5E02486680-05
JogBackward
102BTechnology instructions
9.3 Basic motion control
389